Hello all,
Tmima Pliroforikis Perifereiakis Enotitas Pierias wrote:
Arnaud Quette wrote:
once Fred has provided you the new binary, please do the same tests
and send back the output trace.
just received the new executable. Trying it out, produced the following.
Please note that I have
2012/5/24 Tmima Pliroforikis Perifereiakis Enotitas Pierias
plirofor...@pieria.pkm.gov.gr:
Hello Arnaud and all,
Hi Michail,
just a bump/heads up to check whether my previous message that contained a
log from running shutdown.return, using the blazer_ser driver...
you did well!
looking at
Arnaud Quette wrote:
2012/5/24 Tmima Pliroforikis Perifereiakis Enotitas Pierias
plirofor...@pieria.pkm.gov.gr:
just a bump/heads up to check whether my previous message that contained a
log from running shutdown.return, using the blazer_ser driver...
you did well!
Glad to hear that! :)
Hello Arnaud and all,
just a bump/heads up to check whether my previous message that contained
a log from running shutdown.return, using the blazer_ser driver...
If something more is needed, please do not hesitate to ask...
Tmima Pliroforikis Perifereiakis Enotitas Pierias wrote:
Arnaud
2012/5/16 Tmima Pliroforikis Perifereiakis Enotitas Pierias
plirofor...@pieria.pkm.gov.gr:
Frédéric Bohé wrote:
On Mon, 2012-05-14 at 13:20 +0300, Tmima Pliroforikis Perifereiakis
Enotitas Pierias wrote:
Hello Frederic,
Frédéric Bohé wrote:
[snip]
offdelay = value
Arnaud Quette wrote:
to confirm this, simply use upsrw to send a shutdown.return command.
having the driver running in debug mode, I'd like to see the related traces.
if it works, I'll check for making shutdown.cancel failure non fatal
(Ie, optional).
Would you be kind enough and explain what
2012/5/16 Tmima Pliroforikis Perifereiakis Enotitas Pierias
plirofor...@pieria.pkm.gov.gr:
Arnaud Quette wrote:
to confirm this, simply use upsrw to send a shutdown.return command.
having the driver running in debug mode, I'd like to see the related
traces.
if it works, I'll check for making
Frédéric Bohé wrote:
On Mon, 2012-05-14 at 13:20 +0300, Tmima Pliroforikis Perifereiakis
Enotitas Pierias wrote:
Hello Frederic,
Frédéric Bohé wrote:
[snip]
offdelay = value
Time to wait before shutting down the UPS (seconds). This
value
is truncated to
Hello Frederic,
Frédéric Bohé wrote:
[snip]
And some more questions:
1) Upon reception of a shutdown command, my server takes approx. 60 for
shutdown. Can I set on this Windows server the ups itself to power down
after say 90? According to the upsc output above, the ups has set
On Mon, 2012-05-14 at 13:20 +0300, Tmima Pliroforikis Perifereiakis
Enotitas Pierias wrote:
Hello Frederic,
Frédéric Bohé wrote:
[snip]
And some more questions:
1) Upon reception of a shutdown command, my server takes approx. 60 for
shutdown. Can I set on this Windows server the ups
Charles Lepple wrote:
On May 10, 2012, at 3:11 AM, Tmima Pliroforikis Perifereiakis Enotitas Pierias
wrote:
1) Any ideas on why battery.charge is set to -24.8 (note also the negative sign)
The bestups driver does not have a lot of debugging information, and when
that driver was written, it
Hello all,
been 5 years since I posted on this list, glad to be back :)
I have a number of X-power Tigra 1kVA online UPS units. From some
knowledgeable folks working for the local distributor, I learnt that
from inside this looked like a Best 610 ups unit.
Before, I had this UPS hooked via
Hello Michail,
On Thu, 2012-05-10 at 10:11 +0300, Tmima Pliroforikis Perifereiakis
Enotitas Pierias wrote:
Hello all,
been 5 years since I posted on this list, glad to be back :)
I have a number of X-power Tigra 1kVA online UPS units. From some
knowledgeable folks working for the local
On May 10, 2012, at 3:11 AM, Tmima Pliroforikis Perifereiakis Enotitas Pierias
wrote:
1) Any ideas on why battery.charge is set to -24.8 (note also the negative
sign)
The bestups driver does not have a lot of debugging information, and when
that driver was written, it was also not possible