Hi everyone, Juniper docs claim this about the power system for an MX480: "Each inlet requires a dedicated AC power feed and a dedicated 15 A (250 VAC) circuit breaker." This seems silly - so long as we're careful not to overload any circuits and pull from diverse panels, why would they care?
Does Juniper have a good reason to require this, or are they just trying to prevent people from plugging all four PEMs into the same circuit and thinking that they are redundant? Any suggestions for good AC distribution gear? APC AP9570 looks like what I'd use if left to my own. Thanks, Ross