You will have to manually redispatch something else to keep your voltage within limits (i.e. generator voltage set-points, transformer taps, generator real power dispatch). You may be able to define an OPF with appropriately specified limits on bus voltages, generator P and Q dispatches, etc. that will accomplish what you want automatically.
-- Ray Zimmerman Senior Research Associate B30 Warren Hall, Cornell University, Ithaca, NY 14853 USA phone: (607) 255-9645 On Sep 2, 2014, at 6:15 AM, karthikai dharma <gdkkan...@yahoo.co.in> wrote: > Dear sir, > when i enforce q limits in load flow, the voltage of PV bus goes beyond the > upper limit(>1.1). what i have to do to keep both Q lims and Voltage lims > within the tolerance. > > D.Karthikaikannan > Associate Professor GrI, > Department of Electrical and Electronics Engg > Indra Ganesan College of Engg, > TamilNadu > INDIA