You will have to manually redispatch something else to keep your voltage within 
limits (i.e. generator voltage set-points, transformer taps, generator real 
power dispatch). You may be able to define an OPF with appropriately specified 
limits on bus voltages, generator P and Q dispatches, etc. that will accomplish 
what you want automatically. 

-- 