> Hi,
> By setting it to 1, you will check for generator Var limits and bus-type
switching will take place accordingly with simultaneous conversions. The
option 2 switches only one bus at a time. By default (option 0) generator
Var limits are not checked.
>
> Regards,
> Shruti
>
> On Sep 20, 2015 1:38 AM, "rainy chung" <chunyu...@gmail.com> wrote:
>>
>> hi everyone,
>>
>> when using mpoption to define the power flow running manner, what's the
difference between setting mpopt=mpoption(mpopt,'pf.enforce_q_lims',1) and
without specifying it. Thanks!