Hello, I have a TrippLite SMART1500RMXL2U that I'm trying to get running with Nut 2.2.1.
Running upsdrvctl start works, upsd works, but upsc has "issues": je-nas:~/src/nut-2.2.1# upsdrvctl start Network UPS Tools - UPS driver controller 2.2.1- Network UPS Tools - Tripp Lite OMNIVS and SMARTPRO driver 0.11 (2.2.1-) Warning: This is an experimental driver. Some features may not function correctly. Detected a UPS: TRIPP LITE/ Tripp Lite SMART1500RMXL2U Unit ID: 257 Unknown protocol (4)Attached to Tripp Lite Tripp Lite SMART1500RMXL2U je-nas:~/src/nut-2.2.1# upsd Network UPS Tools upsd 2.2.1- listening on 0.0.0.0 port 3493 Connected to UPS [UPS]: tripplite_usb-UPS //share/cmdvartab not found - disabling descriptions je-nas:~/src/nut-2.2.1# upsc [EMAIL PROTECTED] battery.voltage.nominal: 48 driver.name: tripplite_usb driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.version: 2.2.1- driver.version.internal: 0.11 input.voltage.nominal: 120 outlet.1.desc: Load 1 outlet.1.id: 1 outlet.1.switch: 1 outlet.1.switchable: 1 outlet.2.desc: Load 2 outlet.2.id: 2 outlet.2.switchable: 0 ups.debug.0: 00 04 58 58 58 58 0d '..XXXX.' ups.debug.D: 37 36 38 38 0d 00 00 '7688...' ups.debug.L: 30 32 43 30 45 34 0d '02C0E4.' ups.debug.load_banks: 1 ups.debug.M: 36 46 37 42 0d 00 00 '6F7B...' ups.debug.S: 31 34 30 32 31 30 0d '140210.' ups.debug.T: 38 46 30 32 35 37 0d '8F0257.' ups.debug.V: 31 30 38 31 0d 00 00 '1081...' ups.delay.shutdown: 64 ups.firmware: F0970.B ups.firmware.aux: protocol 0004 ups.id: 257 ups.mfr: Tripp Lite ups.model: Tripp Lite SMART1500RMXL2U ups.power.nominal: 150 ups.status: Here's some debug ouput from tripplite_usb: je-nas:~/src/nut-2.2.1# /bin/tripplite_usb -a UPS -DDDD Network UPS Tools - Tripp Lite OMNIVS and SMARTPRO driver 0.11 (2.2.1-) Warning: This is an experimental driver. Some features may not function correctly. debug level is '4' Checking device (0000/0000) (003/001) - VendorID: 0000 - ProductID: 0000 - Manufacturer: unknown - Product: unknown - Serial Number: unknown - Bus: 003 Trying to match device Device does not match - skipping Checking device (09AE/0001) (002/004) - VendorID: 09ae - ProductID: 0001 - Manufacturer: TRIPP LITE - Product: Tripp Lite SMART1500RMXL2U - Serial Number: unknown - Bus: 002 Trying to match device Device matches Detected a UPS: TRIPP LITE/ Tripp Lite SMART1500RMXL2U send_cmd(msg_len=3, type='W') send_cmd(msg_len=2, type=' send_cmd(msg_len=2, type='S') send_cmd(msg_len=2, type='P') send_cmd(msg_len=2, type='F') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='U') Unit ID: 257 Unknown protocol (4)Attached to Tripp Lite Tripp Lite SMART1500RMXL2U send_cmd(msg_len=2, type='S') send_cmd(msg_len=2, type='L') send_cmd(msg_len=2, type='D') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='M') send_cmd(msg_len=2, type='T') dstate_init: sock /var/state/ups/tripplite_usb-UPS open on fd 5 send_cmd(msg_len=2, type='S') send_cmd(msg_len=2, type='L') send_cmd(msg_len=2, type='D') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='M') send_cmd(msg_len=2, type='T') send_cmd(msg_len=2, type='S') send_cmd(msg_len=2, type='L') send_cmd(msg_len=2, type='D') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='M') send_cmd(msg_len=2, type='T') send_cmd(msg_len=2, type='S') send_cmd(msg_len=2, type='L') send_cmd(msg_len=2, type='D') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='M') send_cmd(msg_len=2, type='T') send_cmd(msg_len=2, type='S') send_cmd(msg_len=2, type='L') send_cmd(msg_len=2, type='D') send_cmd(msg_len=2, type='V') send_cmd(msg_len=2, type='M') send_cmd(msg_len=2, type='T') Signal 2: exiting Any tips on getting this working fully? Is it something I've done, or does the code just not know exactly how to talk to this particular model? Justin _______________________________________________ Nut-upsuser mailing list [email protected] http://lists.alioth.debian.org/mailman/listinfo/nut-upsuser