Hi, I have simple configuration: one master with one UPS connected via serial port, and five slaves. When battery is low and master set FSD on UPS, then after few seconds it get from all slaves: "disconnected (read failure)" and start shutdown and power off before slave shutdown complete, that need about 90 seconds. I don't understand, why slaves disconnected before shutdown go near it's finish. I have checked this: it is not init or init script that kill upsmon, but upsmon itself close connection right after get "force shutdown" from master.