Seems as sensors stored in uncommon Oids,
currently unsupported.

Same way as adding support for new OS/Hardware.

Create Jira issue here: https://jira.observium.org/secure/CreateIssue!default.jspa <https://jira.observium.org/secure/CreateIssue%21default.jspa>

Make and attach full snmpdump from device as:
snmpwalk -v2c -c <community> -Cc --hexOutputLength=0 -Ih -ObentxU <hostname> .1 > myagent.snmpwalk snmpwalk -v2c -c <community> -Cc --hexOutputLength=0 -Ih -ObentxU <hostname> .1.3.6.1.4.1 >> myagent.snmpwalk

If device not support SNMP version 2c, replace -v2c with -v1.


promise kumalo via observium wrote on 28.08.2023 12:16:
Hello

i am having trouble adding the  new APC EPDU1132M to the observium. The device is being added and recognised as an APC PDU, but there are no power readings being recorded.

i have added an old model APC AP7854 B2 to observium and its works perfectly, i can see the power readings.

i am running obversium CE 23.1.12493.


_______________________________________________
observium mailing list -- observium@lists.observium.org
To unsubscribe send an email to observium-le...@lists.observium.org

--
Mike Stupalov,
Discord channel: https://discord.gg/GjpNXKWm8W
Observium Limited, https://observium.org

_______________________________________________
observium mailing list -- observium@lists.observium.org
To unsubscribe send an email to observium-le...@lists.observium.org

Reply via email to