Greetings everyone,

 

I have  Liebert UPS that I am trying to setup SNMP traps for and for
some reason OpsView will not see the MIBS.

 

I loaded them (the mibs) and can query the unit from the OpsView server
and have proper names returned, but when the unit actually sends a trap
I keep getting Trapname not fully translated.

 

I tried running the command line script to promote one of the Liebert
mibs and got the following:

 

./promote_mib LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventNotifications.0.2

Looking for LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventNotifications.0.2

Found in module LIEBERT-GP-NOTIFICATIONS-MIB as lgpEventNotifications

FQN=LIEBERT-GP-NOTIFICATIONS-MIB::lgpEventNotifications

No MIBS needed to copy

 

 

I do this and the next time I get a trap I get the same message.  All of
the Liebert MIBS are there and work.  What am I doing wrong here or
where else can I look.  I am stuck.

 

 

snmpwalk -v 2c -c COMMUNITY LIEBERTUPS .enterprises

LIEBERT-GP-AGENT-MIB::lgpAgentIdentManufacturer.0 = STRING: Liebert
Corporation

LIEBERT-GP-AGENT-MIB::lgpAgentIdentModel.0 = STRING: IntelliSlot Web/485
Card

LIEBERT-GP-AGENT-MIB::lgpAgentIdentFirmwareVersion.0 = STRING: 3.120.7

LIEBERT-GP-AGENT-MIB::lgpAgentIdentSerialNumber.0 = STRING:
416791G411T2008NOV130242

LIEBERT-GP-AGENT-MIB::lgpAgentIdentPartNumber.0 = STRING: OCWEB-ADPT

LIEBERT-GP-AGENT-MIB::lgpAgentDeviceIndex.1 = INTEGER: 1

LIEBERT-GP-AGENT-MIB::lgpAgentDeviceId.1 = OID:
LIEBERT-GP-REGISTRATION-MIB::lgpNpower

LIEBERT-GP-AGENT-MIB::lgpAgentDeviceManufacturer.1 = STRING: Liebert
Corporation

LIEBERT-GP-AGENT-MIB::lgpAgentDeviceModel.1 = STRING: Npower

LIEBERT-GP-AGENT-MIB::lgpAgentDeviceFirmwareVersion.1 = STRING: V 1.28

LIEBERT-GP-AGENT-MIB::lgpAgentDeviceUnitNumber.1 = INTEGER: 1

LIEBERT-GP-AGENT-MIB::lgpAgentReboot.0 = INTEGER: 0

LIEBERT-GP-CONDITIONS-MIB::lgpConditionsPresent.0 = Gauge32: 0

LIEBERT-GP-POWER-MIB::lgpPwrConfigLowBatteryWarningTime.0 = INTEGER: 5
minutes

LIEBERT-GP-POWER-MIB::lgpPwrBatteryTimeRemaining.0 = INTEGER: 65535
minutes

LIEBERT-GP-POWER-MIB::lgpPwrBatteryCapacity.0 = INTEGER: 100 percent

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointId.1 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrSource1Input

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointId.2 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrMeasBypass

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointId.3 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoad

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNumLines.1 = INTEGER: 3
Count

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNumLines.2 = INTEGER: 3
Count

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNumLines.3 = INTEGER: 3
Count

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomVolts.1 = INTEGER: 480
Volt

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomVolts.2 = INTEGER: 480
Volt

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomVolts.3 = INTEGER: 208
Volt

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomFrequency.1 = INTEGER: 60
Hertz

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomFrequency.3 = INTEGER: 60
Hertz

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointFrequency.1 = INTEGER: 60
Hertz

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointFrequency.2 = INTEGER: 60
Hertz

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointFrequency.3 = INTEGER: 60
Hertz

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomPowerFactor.3 = INTEGER:
0 .01 Power Factor

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointNomVA.3 = INTEGER: 50000
Volt-Amp

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.1.1 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrSource1Input

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.1.2 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrSource1Input

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.1.3 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrSource1Input

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.2.1 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrMeasBypass

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.2.2 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrMeasBypass

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.2.3 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrMeasBypass

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.3.1 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoad

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.3.2 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoad

LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPoint.3.3 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoad

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.1.1 = INTEGER: 485
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.1.2 = INTEGER: 486
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.1.3 = INTEGER: 483
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.2.1 = INTEGER: 485
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.2.2 = INTEGER: 484
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.2.3 = INTEGER: 482
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.3.1 = INTEGER: 208
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.3.2 = INTEGER: 208
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLL.3.3 = INTEGER: 208
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN.3.1 = INTEGER: 120
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN.3.2 = INTEGER: 120
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN.3.3 = INTEGER: 120
Volt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent.1.1 = INTEGER: 36 Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent.1.2 = INTEGER: 37 Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent.1.3 = INTEGER: 37 Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent.3.1 = INTEGER: 74 Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent.3.2 = INTEGER: 39 Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementCurrent.3.3 = INTEGER: 61 Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVA.3.1 = INTEGER: 9000
Volt-Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVA.3.2 = INTEGER: 5000
Volt-Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVA.3.3 = INTEGER: 7000
Volt-Amp

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementTruePower.3.1 = INTEGER: 9000
Watt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementTruePower.3.2 = INTEGER: 5000
Watt

LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementTruePower.3.3 = INTEGER: 7000
Watt

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointId.1 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrMeasBattery

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointId.2 = OID:
LIEBERT-GP-POWER-MIB::lgpPwrMeasDcBus

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointSubID.1 = INTEGER: 1 Count

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointSubID.2 = INTEGER: 1 Count

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointVolts.1 = INTEGER: 532
Volt

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointCurrent.1 = INTEGER: 0 Amp

LIEBERT-GP-POWER-MIB::lgpPwrDcMeasurementPointNomVolts.2 = INTEGER: 540
Volt

LIEBERT-GP-POWER-MIB::lgpPwrUPSTopDualInput.0 = INTEGER: no(2)


--
Confidentiality Notice: This e-mail, including attachments, may include 
confidential and/or proprietary information, and may be used only by the person 
or entity to which it is addressed. If the reader of this e-mail is not the 
intended recipient or his or her authorized agent, the reader is hereby 
notified that any dissemination, distribution, copying or taking any action in 
reliance upon this information is prohibited. If you have received this e-mail 
in error, please notify the sender by replying to this message and delete this 
e-mail immediately.
This message was scanned by ESVA and is believed to be clean.


_______________________________________________
Opsview-users mailing list
[email protected]
http://lists.opsview.org/lists/listinfo/opsview-users

Reply via email to