Am 28.04.2014 13:50, schrieb Johan Ström: > > Mostly this has been working good, with reliable triggering of the > latch. However, one problem with pull-up based circuit is that I get > erroneous triggers if VCC disappears, for example due to a bus > disconnect, > > So.. my questions would be: > a) what does your DS2406/08-setup look like, and have you had any > similar problems? > With a DS2408, I would always check the POR flag and sort out errorneous latch states in the software.
With a DS2406, there isn't such a POR flag, but you can check the status byte 7 whether it is in factory setting. That would mean POR. This only works when you don't use the correspoding setting "Respond to conditional search when PIO A or B is high". Kind regards Jan ------------------------------------------------------------------------------ "Accelerate Dev Cycles with Automated Cross-Browser Testing - For FREE Instantly run your Selenium tests across 300+ browser/OS combos. Get unparalleled scalability from the best Selenium testing platform available. Simple to use. Nothing to install. Get started now for free." http://p.sf.net/sfu/SauceLabs _______________________________________________ Owfs-developers mailing list Owfs-developers@lists.sourceforge.net https://lists.sourceforge.net/lists/listinfo/owfs-developers