Solar converters used to make a DC regulated SS power supply, I'd check them.

http://www.solarconverters.com/index.html

jay 
peltz power
On Nov 4, 2011, at 8:01 AM, John DeBoever wrote:

> Jeremy,
>  
> I understand that your application wants the wireless communication load to 
> operate at 24VDC with a voltage tolerance of +-4V (15%).  Since your battery 
> bank will operate between voltages larger than +-15%, you will need typically 
>  22-30V/24V  DC/DC converter with max 15% voltage tolerance output, wired 
> between your 24V configured battery bank DC output and your wireless 
> communication load.
> Some DC/DC converter OEM suggestions that offer tighter voltage tolerances 
> (0.5 to 1%):
> http://analyticsystems.com/products/dc_convert/
>  
> http://www.meanwelldirect.co.uk/products/200W-24V-Input-Single-Output-DC-DC-Converter/SD-200B-Series/default.htm
> John
> John F. DeBoever
> Global Technical Director – Renewable Energy
> Trojan Battery Company
>  
> 12380 Clark Street
> Santa Fe Springs, CA 90670
> Tel: +1-562-236-3000 Ext. 3139
> Fax: +1-562-236-3239
> jdeboe...@trojanbattery.com
> www.trojanbattery.com
>  