Re: Stus-List Refrig

2018-07-13 Thread Bruno Lachance via CnC-List
If you have fast frosting after you start the system, the compressor or a leak 
might not be the problem, have you replaced the evaporator too 3 years ago? 
Then can clog and give you uneven frosting. I heard that some people/ pro can 
clean/purge them, but once it stats it might happen again and should be 
replaced.

Bruno Lachance
Bécassine, 33 mkII
New Richmond, Qc

Envoyé de mon iPad

Le 13 juil. 2018 à 21:43, Persuasion37 via CnC-List 
mailto:cnc-list@cnc-list.com>> a écrit :

Sorry I have limited data.  But there is a way to connect a led light to the 
controller to see if there are any faults.  Just google it.  Mine was the 
controller.

Mike
PERSUASION
C 37 K/CB
Long Sault

On Jul 13, 2018, at 6:47 PM, David via CnC-List 
mailto:cnc-list@cnc-list.com>> wrote:

So.  3 year old old Danfoss 12 volt refrig.   Last one lasted us  20 plus 
years.  This one...?   Worked great until this year.  Start it up.  Fan is 
going and we get frosting at the evaporator at where the tubes enter.   But not 
consistent throughout evaporator.  If a coolant leak would we get any frosting 
of evap at all?

Voltage is 12.5 or better .

Thanks in advance.

Get Outlook for Android

___

Thanks everyone for supporting this list with your contributions.  Each and 
every one is greatly appreciated.  If you want to support the list - use PayPal 
to send contribution --   https://www.paypal.me/stumurray

___

Thanks everyone for supporting this list with your contributions.  Each and 
every one is greatly appreciated.  If you want to support the list - use PayPal 
to send contribution --   https://www.paypal.me/stumurray

___

Thanks everyone for supporting this list with your contributions.  Each and 
every one is greatly appreciated.  If you want to support the list - use PayPal 
to send contribution --   https://www.paypal.me/stumurray



Re: Stus-List Refrig

2018-07-13 Thread Persuasion37 via CnC-List
Sorry I have limited data.  But there is a way to connect a led light to the 
controller to see if there are any faults.  Just google it.  Mine was the 
controller.

Mike
PERSUASION
C 37 K/CB
Long Sault

> On Jul 13, 2018, at 6:47 PM, David via CnC-List  wrote:
> 
> So.  3 year old old Danfoss 12 volt refrig.   Last one lasted us  20 plus 
> years.  This one...?   Worked great until this year.  Start it up.  Fan is 
> going and we get frosting at the evaporator at where the tubes enter.   But 
> not consistent throughout evaporator.  If a coolant leak would we get any 
> frosting of evap at all?  
> 
> Voltage is 12.5 or better .
> 
> Thanks in advance.  
> 
> Get Outlook for Android
> 
> ___
> 
> Thanks everyone for supporting this list with your contributions.  Each and 
> every one is greatly appreciated.  If you want to support the list - use 
> PayPal to send contribution --   https://www.paypal.me/stumurray
> 
___

Thanks everyone for supporting this list with your contributions.  Each and 
every one is greatly appreciated.  If you want to support the list - use PayPal 
to send contribution --   https://www.paypal.me/stumurray



Stus-List Refrig

2018-07-13 Thread David via CnC-List
So.  3 year old old Danfoss 12 volt refrig.   Last one lasted us  20 plus 
years.  This one...?   Worked great until this year.  Start it up.  Fan is 
going and we get frosting at the evaporator at where the tubes enter.   But not 
consistent throughout evaporator.  If a coolant leak would we get any frosting 
of evap at all?

Voltage is 12.5 or better .

Thanks in advance.

Get Outlook for Android