questions on mpoption
hi everyone, when using mpoption to define the power flow running manner, what's the difference between setting mpopt=mpoption(mpopt,'pf.enforce_q_lims',1) and without specifying it. Thanks!
Re: questions on mpoption
I made an experiment, it seemed the VAR limits with and without specifying this are the same. 2015-09-20 16:43 GMT+08:00 Shruti Rao <sra...@asu.edu>: > > > Hi, > > By setting it to 1, you will check for generator Var limits and bus-type > switching will take place accordingly with simultaneous conversions. The > option 2 switches only one bus at a time. By default (option 0) generator > Var limits are not checked. > > > > Regards, > > Shruti > > > > On Sep 20, 2015 1:38 AM, "rainy chung" <chunyu...@gmail.com> wrote: > >> > >> hi everyone, > >> > >> when using mpoption to define the power flow running manner, what's the > difference between setting mpopt=mpoption(mpopt,'pf.enforce_q_lims',1) and > without specifying it. Thanks! >
Re: questions on optimal power flow
Thanks Sir, I will try that. By the way, I am wondering whether you know how to add new varaibles z using direct specification method? Many thanks! Best Regards! 2015-08-11 6:35 GMT+08:00 Carleton Coffrin carleton.coff...@nicta.com.au: You can modify the test case so that the bounds are very tight on the variables you would like to keep constant. Cheers, -Carleton On Aug 10, 2015, at 9:53 PM, rainy chung chunyu...@gmail.com wrote: Hi Matpower communities, The default runopf change all the control inputs, such as active power and terminal voltage of PV buses. Is it possible to only change the values of a specific subsets of , for example, PV bus instead of all of it! Many Thanks! Best Regards! The information in this e-mail may be confidential and subject to legal professional privilege and/or copyright. National ICT Australia Limited accepts no liability for any damage caused by this email or its attachments.
questions on optimal power flow
Hi Matpower communities, The default runopf change all the control inputs, such as active power and terminal voltage of PV buses. Is it possible to only change the values of a specific subsets of , for example, PV bus instead of all of it! Many Thanks! Best Regards!