We have a new pop going up im putting the enclosure in tommorrow.
We get our power from a secondary distribution panel on the leg. This penel
is not directly grounded locally, there is metal conduit going into the
ground where it gets its feed from the primary somewhere else. There is a 4
o6 6 gua
I did a ground rod for a similar situation.
Josh Luthman
Office: 937-552-2340
Direct: 937-552-2343
1100 Wayne St
Suite 1337
Troy, OH 45373
On Jun 24, 2015 5:53 PM, "That One Guy /sarcasm"
wrote:
> We have a new pop going up im putting the enclosure in tommorrow.
>
> We get our power from a secon
I would go with your first plan of bonding your cabinet to the electrical
ground / steel conduit versus adding a grounding rod. I think you are going
to be better off not having a secondary ground path.