[AFMUG] bonding ground at grain leg

2015-06-24 Thread That One Guy /sarcasm
We have a new pop going up im putting the enclosure in tommorrow. We get our power from a secondary distribution panel on the leg. This penel is not directly grounded locally, there is metal conduit going into the ground where it gets its feed from the primary somewhere else. There is a 4 o6 6 gua

Re: [AFMUG] bonding ground at grain leg

2015-06-24 Thread Josh Luthman
I did a ground rod for a similar situation. Josh Luthman Office: 937-552-2340 Direct: 937-552-2343 1100 Wayne St Suite 1337 Troy, OH 45373 On Jun 24, 2015 5:53 PM, "That One Guy /sarcasm" wrote: > We have a new pop going up im putting the enclosure in tommorrow. > > We get our power from a secon

Re: [AFMUG] bonding ground at grain leg

2015-06-25 Thread Mark Radabaugh
I would go with your first plan of bonding your cabinet to the electrical ground / steel conduit versus adding a grounding rod. I think you are going to be better off not having a secondary ground path. Mark > On Jun 24, 2015, at 5:53 PM, That One Guy /sarcasm > wrote: > > We have a new p