Re: Raised Floors

2019-05-25 Thread Adrian Stoness via cctalk
> > acid water hah i work around ph 2.38 water liming it during the summer. > insane how fast it will eat steel out >

Re: Raised Floors

2019-05-25 Thread Stefan Skoglund via cctalk
fre 2019-05-24 klockan 23:38 -0700 skrev Chuck Guzis via cctalk: > On 5/24/19 9:12 PM, Carlos E Murillo-Sanchez via cctalk wrote: > > > Sulfuric acid is hard to wash off; the amount that made it to the > > room > > must have been pretty small, otherwise people couldn't be allowed > > in. > >

Re: Raised Floors

2019-05-25 Thread Chuck Guzis via cctalk
On 5/24/19 9:12 PM, Carlos E Murillo-Sanchez via cctalk wrote: > Sulfuric acid is hard to wash off; the amount that made it to the room > must have been pretty small, otherwise people couldn't be allowed in.  > And, if it was bad enough to corrode boards, imagine what that would do > to your

Re: Raised Floors

2019-05-24 Thread Carlos E Murillo-Sanchez via cctalk
Mark Matlock via cctalk wrote: The discussion on raised floors in data centers reminded me of an interesting past experience. My company had installed its first supervisory process control system in an enzyme plant. The plant had been around for quite some time and the process control

Re: Raised Floors

2019-05-24 Thread Carlos E Murillo-Sanchez via cctalk
Mark Matlock via cctalk wrote: The discussion on raised floors in data centers reminded me of an interesting past experience. My company had installed its first supervisory process control system in an enzyme plant. The plant had been around for quite some time and the process control

Re: Raised Floors

2019-05-24 Thread Paul Koning via cctalk
> On May 24, 2019, at 12:35 PM, Mark Matlock via cctalk > wrote: > > The discussion on raised floors in data centers reminded me of an > interesting past experience. My company had installed its first supervisory > process control system in an enzyme plant. ... > &

RE: Raised Floors

2019-05-24 Thread Mark Matlock via cctalk
The discussion on raised floors in data centers reminded me of an interesting past experience. My company had installed its first supervisory process control system in an enzyme plant. The plant had been around for quite some time and the process control system was part of a retrofit

Re: Raised Floors

2019-05-23 Thread Craig Ruff via cctalk
I should have been more clear in my last response. The 2x2 grid of the floor tiles does not extend to the floor, but to an intermediate layer with wider spacing of the supports at the floor level.

Re: Raised Floors

2019-05-23 Thread Grant Taylor via cctalk
On 5/23/19 5:25 PM, Craig Ruff via cctech wrote: I should have been more clear in my last response. The 2x2 grid of the floor tiles does not extend to the floor, but to an intermediate layer with wider spacing of the supports at the floor level. Thank you for the clarification. I expected

RE: Raised Floors

2019-05-23 Thread Wayne S via cctalk
osts<mailto:cctalk@classiccmp.org> Subject: Re: Raised Floors > Purdue's insurer REQUIRES fire sprinklers in data centers. And it's not > atypical from what I've heard. They are all dry, pre-action systems, which > eliminate most of the danger of it accidentally dumping water. It's >

Re: Raised Floors

2019-05-23 Thread Ethan O'Toole via cctalk
Purdue's insurer REQUIRES fire sprinklers in data centers. And it's not atypical from what I've heard. They are all dry, pre-action systems, which eliminate most of the danger of it accidentally dumping water. It's unlikely that with a dry pipe, pre-action system water will be dumped somewhere

Re: Raised Floors

2019-05-23 Thread Grant Taylor via cctalk
On 5/22/19 9:41 AM, Grant Taylor via cctalk wrote: Both of the data centers / raised floors in my office have fire sprinklers.  I don't know if they lines are charged or dry.  (I'll inquire.) I received an answer this morning stating that the fire sprinklers in the DC are "charged wit

Re: Raised Floors

2019-05-22 Thread Craig Ruff via cctalk
> On May 22, 2019, at 11:00 AM, cctech-requ...@classiccmp.org wrote: > From: Grant Taylor > > On 5/21/19 5:33 PM, Craig Ruff via cctech wrote: >> The NCAR Wyoming Supercomputer Center has raised floors of about 20 feet. > > Did the support posts go all the way down?

Re: Raised Floors

2019-05-22 Thread Grant Taylor via cctalk
On 5/22/19 5:46 PM, Craig Ruff via cctech wrote: It was moderately open below the floor, there are columns that support the grid. The raised floor at work has posts (I guess you could call them columns) at the corner of every tile that run down to the floor. This is why I'm asking if the

Re: Raised Floors

2019-05-22 Thread Grant Taylor via cctalk
On 5/22/19 9:08 AM, Patrick Finnegan via cctalk wrote: Purdue's insurer REQUIRES fire sprinklers in data centers. Both of the data centers / raised floors in my office have fire sprinklers. I don't know if they lines are charged or dry. (I'll inquire.) The local fire department does

Re: Raised Floors

2019-05-22 Thread Christian Corti via cctalk
On Wed, 22 May 2019, Chuck Guzis wrote: So how are data centers cooled with water now? Does the water cool coldplates directly? Sort of, see for example the Rittal LCP system. I've had only a couple of instances where cooling water was used. In All current high-density rack systems need

Re: Raised Floors

2019-05-22 Thread Patrick Finnegan via cctalk
On Wed, May 22, 2019 at 3:43 AM Jim Manley via cctalk wrote: > Someone should be sued and go to prison for signing off on permits that > would allow water to get anywhere near a DC - it's a violation of the > National Electric Code, for starters. If anyone sees something like that, > it should

Re: Raised Floors

2019-05-22 Thread Paul Berger via cctalk
On 2019-05-22 10:00 a.m., Paul Koning via cctalk wrote: On May 22, 2019, at 6:57 AM, Stefan Skoglund via cctalk wrote: ons 2019-05-22 klockan 08:45 + skrev Wayne S via cctalk: ... Funny, but Halon is outlawed and having it around did seem to bother them. It was replaced with some

Re: Raised Floors

2019-05-22 Thread Paul Koning via cctalk
> On May 22, 2019, at 6:57 AM, Stefan Skoglund via cctalk > wrote: > > ons 2019-05-22 klockan 08:45 + skrev Wayne S via cctalk: >> ... >> Funny, but Halon is outlawed and having it around did seem to bother >> them. It was replaced with some other gas system that i can't >> remember the

Re: Raised Floors

2019-05-22 Thread Tor Arntsen via cctalk
On Wed, 22 May 2019 at 10:34, Stefan Skoglund via cctalk wrote: > Halon should be completely and fully illegal in civilian installations. In 1990 or 1991 I was inside a computer room when somebody accidentally pushed an elbow into the fire emergency button.. and the halon went off. Big room,

Re: Raised Floors

2019-05-22 Thread Stefan Skoglund via cctalk
ons 2019-05-22 klockan 08:45 + skrev Wayne S via cctalk: > All true. Just sayin' that water can get into the DC even when it's > not intended. > When fighting a fire in another part of a structure, the water may > find it's way into the DC. > > Not sure about not allowing water to get near

Re: Raised Floors

2019-05-22 Thread Wayne S via cctalk
s are for, and the media, if no >> action occurs with the hotlines - we're talking about the possibility of >> serious injury and death here. >> >> >> On Tue, May 21, 2019 at 11:12 PM Grant Taylor via cctalk < >> cctalk@classiccmp.org> wrote: >> >>>&

Re: Raised Floors

2019-05-22 Thread Wayne S via cctalk
ithin the organization, since >>> the facilities people are either incompetent or complicit in keeping quiet >>> about it. That's what anonymous.hotlines are for, and the media, if no >>> action occurs with the hotlines - we're talking about the possibility of >>> seriou

Re: Raised Floors

2019-05-22 Thread Wayne S via cctalk
rs with the hotlines - we're talking about the possibility of > serious injury and death here. > > > On Tue, May 21, 2019 at 11:12 PM Grant Taylor via cctalk < > cctalk@classiccmp.org> wrote: > >>> On 5/21/19 5:33 PM, Craig Ruff via cctech wrote: >>> The NCA

Re: Raised Floors

2019-05-22 Thread Stefan Skoglund via cctalk
ons 2019-05-22 klockan 01:42 -0600 skrev Jim Manley via cctalk: > No firefighter in their right mind is going to knowingly pump a drop > of > water anywhere near or in the direction of a data center, let alone > into > it. That's why they're equipped with Halon or other oxygen > displacement, >

Re: Raised Floors

2019-05-22 Thread Jim Manley via cctalk
. On Tue, May 21, 2019 at 11:12 PM Grant Taylor via cctalk < cctalk@classiccmp.org> wrote: > On 5/21/19 5:33 PM, Craig Ruff via cctech wrote: > > The NCAR Wyoming Supercomputer Center has raised floors of about 20 feet. > > Did the support posts go all the way down? Or was ther

RE: Raised Floors

2019-05-21 Thread Wayne S via cctalk
. From: cctech on behalf of Craig Ruff via cctech Sent: Tuesday, May 21, 2019 4:33:07 PM To: cct...@classiccmp.org Subject: Re: Raised Floors The NCAR Wyoming Supercomputer Center has raised floors of about 20 feet. The auxilary cooling and PDUs

Re: Raised Floors

2019-05-21 Thread Grant Taylor via cctalk
On 5/21/19 5:33 PM, Craig Ruff via cctech wrote: The NCAR Wyoming Supercomputer Center has raised floors of about 20 feet. Did the support posts go all the way down? Or was there some sort of grid work that supported the raised floor above an open area that contained the PDUs? I ask

Re: Raised Floors

2019-05-21 Thread Craig Ruff via cctalk
The NCAR Wyoming Supercomputer Center has raised floors of about 20 feet. The auxilary cooling and PDUs are installed down there. Needless to say, you don't pull a floor tile there unless you are on the facility staff!