Hello Boštjan:
I would use a 1:1 transformer with a grounded
shield between primary and secondary.
The transformer core will saturate with differential
mode transients thus reducing the differential mode
transients in the secondary.
The shield will eliminate the capacitance between
primary an
Dear experts,
We have an IT product intended for connection to OVC IV (6kV transients). Input
filter also comprises two IEC 61051-2 certified varistors (L to middle point, N
to middle point) and one GDT (middle point to PE).
Annex G of IEC 60950-1 is saying that we need to measure transient vol