Re: [etherlab-users] Configuring the Ethercat bus via xml

2016-02-10 Thread ronaldo.mercado
Hi, I have no experience with ET9000. For our application [1] we use python to read the ESI files, extract relevant information to a smaller xml configuration. The configuration is parsed to C structures using libxml2 subsequently used in the scanner configuration. HTH, Ronaldo [1]

Re: [etherlab-users] Configuring the Ethercat bus via xml

2016-02-10 Thread ronaldo.mercado
Hi, For Beckhoff devices the ESI files are at this location www.beckhoff.com -> Download -> Configuration files -> EtherCAT Alternatively ftp://ftp.beckhoff.com/Config/ethercat/XML_Device_Description/ Regards, Ronaldo -- This e-mail and any attachments may contain

Re: [etherlab-users] etherlab-users Digest, Vol 104, Issue 1

2016-02-10 Thread David Page
ET1100 Section I.3 Frame Processing: It is not possible to use unmanaged switches between these ESCs or between master and the first slave, because source and destination MAC addresses are not evaluated or exchanged by the ESCs. Only the source MAC address is modified when using the default