Hi Mr Bausly, Like Asier, I also want to control Omron NX-ECC01 IO coupler too. As instructed in your mail, I configured the coupler using Sysmac Studio. I also used the --enable-sii-assign option and recompile the EtherLab master. But I still don't get the PDO configuration for the IO devic

Re: [etherlab-users] Problems initializing Omron system

2017-03-28 Thread Gavin Lambert
On 28 March 2017 23:21, quoth Asier Tamayo: > After some debug, we have finally got the system working properly. We had > to define EC_SII_ASSIGN in the config.h file and recompile the EtherLab > master. The right way to define this is not to modify config.h directly, but to specify --enable-sii-

Re: [etherlab-users] Problems initializing Omron system

2017-03-28 Thread Asier Tamayo
-users] Problems initializing Omron system 1. Get a copy of Omron’s Sysmac Studio setup software. 2. Connect your PC to the NX Coupler via the USB cable. 3. Create a New Sysmac Studio Project. 4. Within your Sysmac Studio Project configure the “virtual” NX Coupler with the

Re: [etherlab-users] Problems initializing Omron system

2017-03-22 Thread Henry Bausley
1. Get a copy of Omron’s Sysmac Studio setup software. 2. Connect your PC to the NX Coupler via the USB cable. 3. Create a New Sysmac Studio Project. 4. Within your Sysmac Studio Project configure the “virtual” NX Coupler with the slices (“boards”) in exactly the same orde

[etherlab-users] Problems initializing Omron system

2017-03-22 Thread Asier Tamayo
Dear all, We have our Etherlab master running without any problem with Beckhoff boards (digital I/O, analog I/O…). Now, we wanted to make some tests with an Omron system, but we fail to get it running. We seem unable to make it go further than the INIT state. Has anyone got any experience in wo