RE: Iccprt problem

2000-01-13 Thread Wright,Jason
I seem to remember this problem occurring if there is an empty compound in the CP being accessed. Check to see if there is a compound with no blocks in it in this CP and delete it. -Jason -Original Message- From: Joseph S [SMTP:[EMAIL PROTECTED]] Sent: Thursda

RE: Script Execution

2000-03-22 Thread Wright,Jason
If the station is an AP, there is no display manager therefore no DMCMD variable. -Jason -Original Message- From: Schouten, Frits JF [mailto:[EMAIL PROTECTED]] Sent: Wednesday, March 22, 2000 4:52 PM To: 'Foxboro DCS Mail List' Subject: RE: Script Execution How come I get a -45

RE: Failed FBM

2000-06-16 Thread Wright,Jason
Is the new FBM configured to have an extender card? This could cause problems. -Jason -Original Message- From: Craig Rookes [mailto:[EMAIL PROTECTED]] Sent: Thursday, June 15, 2000 5:36 PM To: [EMAIL PROTECTED] Subject: Failed FBM Hi I had a bad fault occur on one of our plant cp,s an

RE: AB KF2 at 19.2 Kbaud?

2000-09-06 Thread Wright,Jason
David, I have seen it this way on account of cable length. Right or wrong, the Site Planning/Installation section of the Integrators for Allen-Bradley Controllers document (B0193RG-C on page 52), "For Reliable communicaition, however, the shorter (20 feet) cable should be used in configurations u