27;
Subject: RE: Alarm Delay
Dan,
It may not be particularly elegant but you could generate a pulse based on
the state change of the CIN block which could start a 5 minute timer in
either ladder logic or a CALC block. The output would be connected to the
INHIB parameter on AIN block. I hope this gi
#x27;Foxboro DCS Mail List'
> Subject: Alarm Delay
>
> Dear List Members,
>
> How can I delay (disable) an AIN block analog alarm for 5 minutes after a
> state change condition in a CIN block is detected?
>
> Thanks,
> Dan
>
> ~~
Dear List Members,
How can I delay (disable) an AIN block analog alarm for 5 minutes after a
state change condition in a CIN block is detected?
Thanks,
Dan
~~~
Dan Karppi CCST
Falconbridge Limited
Smelter Complex
Falconbridge, Ontario
Canada
P0M 1S0
Phone: (705)