Legacy Historian Upgrade

2001-09-27 Thread Bertollini, Paride
Hi, Is anyone of you already experienced with an upgrade of a Legacy historian? Customer needs to make larger his historian, from 500 to 1000 points without loosing his preexisting configuration. Do the saveh50 and loadh50 utilities allow this? Step by step: -saveh50 -recommit with new

RE: Legacy Historian Upgrade

2001-09-27 Thread Johnson, Alex (Foxboro)
] mailto:[EMAIL PROTECTED] -Original Message- From: Bertollini, Paride [SMTP:[EMAIL PROTECTED]] Sent: Thursday, September 27, 2001 7:54 AM To: Foxboro DCS Mail List (E-mail) Subject:Legacy Historian Upgrade Hi, Is anyone

RE: Legacy Historian Upgrade

2001-09-27 Thread Lowell, Tim:
-8362 Fax:610-364-8211 [EMAIL PROTECTED] -Original Message- From: Johnson, Alex (Foxboro) [SMTP:[EMAIL PROTECTED]] Sent: Thursday, September 27, 2001 9:25 AM To: Foxboro DCS Mail List Subject:RE: Legacy Historian Upgrade

RE: Legacy Historian Upgrade

2001-09-27 Thread Johnson, Alex (Foxboro)
:RE: Legacy Historian Upgrade And now a customer perspective... Pros of AIM*Historian: 1. You can modify it while it is running. 2. You can run it on the NT platform as well as AW51, and you can set up remote collectors on both NT and Unix

RE: Legacy Historian Upgrade

2001-09-27 Thread Lowell, Tim:
:RE: Legacy Historian Upgrade Re: Loading The load is proportional to the number of changes and the update rates. What is your setting for fastest_rsr in /opt/fox/ais/bin/foxapi.cfg? This controls how often updates are sent from the CP to the historian

RE: Legacy Historian Upgrade

2001-09-27 Thread Ries, Gerry
, Paride [mailto:[EMAIL PROTECTED]] Sent: Thursday, September 27, 2001 5:54 AM To: Foxboro DCS Mail List (E-mail) Subject: Legacy Historian Upgrade Hi, Is anyone of you already experienced with an upgrade of a Legacy historian? Customer needs to make larger his historian, from 500 to 1000 points

RE: Legacy Historian Upgrade

2001-09-27 Thread Johnson, Alex (Foxboro)
Message- From: Lowell, Tim: [SMTP:[EMAIL PROTECTED]] Sent: Thursday, September 27, 2001 10:04 AM To: 'Foxboro DCS Mail List' Subject:RE: Legacy Historian Upgrade Alex, We have configured most flows to update at 10 seconds, and most

RE: Legacy Historian Upgrade

2001-09-27 Thread Cyrus W. Taft
I am familiar with the Legacy Historian but I was recently at a plant where they had the new AIM* Historian. It was installed on a Sun machine. I really like the fact that you can change its configuration without shutting it down. This allowed us to tighten many deadbands specifically for the

RE: Legacy Historian Upgrade

2001-09-27 Thread Millan, Alexander
Re: foxpai.cfg and fastest_rsr There is a brief description of fastest_rsr in the QF990084 and how you can change it. I have used this variable with FoxAPI. The deafult value is 1 (means 1/2 seconds), every steps means 1/2 sec, i.e., if fastest_rsr = 10, that means 5 seconds. I am not sure if