Yes. You can use exactly the same mechanism, including the unmodified addwind
function to handle solar PV, or any other stochastic generation source, for
that matter.
If you like, you could even make a copy of the addwind.m function and call it
addsolar.m and change “wind” to “solar”
I’m not sure I understand the question. Are you asking if I can provide an
example of a “typical” 24-hour load profile? If so, I’m afraid not. I’m sure
there are many papers and other on-line sources with such data, but you would
have to do some searching and evaluate for yourself which data
For convergence, all islands will need exactly one reference bus, along with
adequate generation to meet any non-curtailable load. Any isolated buses, or
buses in islands that do not meet this criteria, need to have their type set to
NONE (4).
Ray
On Sep 28, 2021, at 11:11 PM, ritu jain