AW: Transformer modelling

2011-09-02 Thread Lemke, André
Dear Dr V. Ravikumar Pandi, First of all thank you for the help. The branch from node 1 to 2 is a transformer. I've entered the ratio 10kV / 0,4 kV = 24 and the phase angle of 150 degrees into the first branch. At this point I can find no error. What struck me when comparing with the case file

Re: AW: Transformer modelling

2011-09-02 Thread Carlos E Murillo-Sanchez
André: The ratio that is to be entered is a tap ratio for transformers that have variable tap ratio capability, not a turns ratio; Tap ratios are usually close to unity, say within [0.95, 1.05] . Turn ratios are done away with in per unit modeling. And phase shifting transformers (a