Running Power flow with Voltage dependent load model

2022-01-10 Thread Arpit Srivastava M.Tech., Electrical Engineering, IIT(BHU)
Hello Matpower Users, Please let me know How to run load flow with voltage dependent load models. In my case each bus load have to be modeled as: Pload= Pl*(V)^pr Qload= Ql*(V)^qr where Pload, Qload = voItage dependent real and reactive power load. Pl, Ql= real and reactive load at nominal voItage.

Fwd: Running Power flow with Voltage dependent load model

2022-01-11 Thread Arpit Srivastava M.Tech., Electrical Engineering, IIT(BHU)
-- Forwarded message - From: Arpit Srivastava M.Tech., Electrical Engineering, IIT(BHU) < arpitsrivastava.ee...@itbhu.ac.in> Date: Mon, Jan 10, 2022 at 3:52 PM Subject: Running Power flow with Voltage dependent load model To: Hello Matpower Users, Please let me know How

Re: Running Power flow with Voltage dependent load model

2022-01-13 Thread Ray Daniel Zimmerman
With MATPOWER 7 and earlier, unfortunately, there isn’t a really clean way to accomplish this. The way that comes to mind is to represent each load with a “fake” generator, and then add some user-defined nonlinear constraints (as described in Section 7.1.2 in the User’s Manual) that define the o