The C-40 tries to hold an equalizing voltage for 4 hours to "complete" the
action. With a system such as you described: big, old bank of questionable
functionality, the c40 could live forever in equalize mode.
-Wes Kennedy
303-653-3073
NABCEPian
--- On Fri, 5/28/10, Mick Abraham
Hi, Detectives~
At a client's off-grid home I observed two side-by-side Trace C-40 PV
controllers, circa 1998, which were "stuck" in equalize mode. Day after day
they did the red/green blink and they would not throttle back the incoming
solar energy. This was with the jumper set for automatic EQ (