My experance is pperhaps to limited with Magnum but I have been impressed with
the surge capacity of the Magnum AE and I assume the PAE is the same. I have
started larger motors than most other inverters, where the others will kick out
on low voltage the magnum seems to hold longer. I have
I have answered an eariler email, but in regards to backfeed, I have back feed
up to 2kW of grid tied inverter into my Magnum 4024 AE and it held grid
specification for the DGI inverter. Above 2kW into the Magnum the Grid tied
inverter kicks out on frequency specification. Other inverters do