Hi, it's me again.
I haven't yet tested my UPS with full load, but I have tried to insert some
values in ups.conf, I have kept the example on the blazer_usb driver help
page:
runtimecal = 240,100,720,50
When I try to start the driver, I receive
root@artu:~# upsdrvctl start
Network UPS Tools -
On Jun 16, 2017, at 2:20 AM, Andrea de Lutti wrote:
> Using 'guestimation' (low: -0.87, high: -1.08)!
> Initial battery charge undetermined
> Driver failed to start (exit status=1)
The "low" and "high" voltages should correspond to the battery voltage when it
is
On Jun 11, 2017, at 8:10 AM, Andrea de Lutti wrote:
>
> What's the right procedure for loading driver/daemon at boot?
> I have read a lot about /var/run/nut missing, but haven't find any
> solution
Your copy of /etc/init.d/nut-server should have the following lines:
#
On 06/15/2017 04:32 PM, Arnaud Quette wrote:
Hello
still no reply from them ...
is the guy you contacted Paul Henri?
I wrote to a generic alias ( Ro-PQSupport ). Got a reply from a fellow
Romanian who also CC:ed something looking like a list
(List-EGPQCO-BUCRO-PQ ). I replied to
Thanks mates,
as suggested I have added
runtimecal = 240,100,720,50
default.battery.voltage.low = 10.4
default.battery.voltage.high = 13.8 (the actual charging voltage)
In ups.conf
I have also added the startup procedure in rc.local file, everything is
fine...
I have only to make a