If you put the PIDU and PTP600 on a cardboard box or other insulating surface, 
can you see –48 VDC on their cases or chassis?

From: Gino Villarini 
Sent: Wednesday, October 07, 2015 2:17 PM
To: af@afmug.com 
Subject: Re: [AFMUG] Issue with a -48 vdc Site! ground loop? Please Help!!

i think so, afaik is floating ground 

On Wed, Oct 7, 2015 at 4:15 PM, Chuck McCown <ch...@wbmfg.com> wrote:

  Is the chassis of the PIDU or the PTP600 connected to your common ground?

  From: Gino Villarini 
  Sent: Wednesday, October 07, 2015 2:14 PM
  To: af@afmug.com 
  Subject: [AFMUG] Issue with a -48 vdc Site! ground loop? Please Help!!

  So we are moving a site form AC to DC -48 

  this is the setup:

  Emerson Rectifier feeding:

  Telco System MPLS router
  Planet Fiber SW
  2 Netonix DC Switches 
  2 SAF POE Injectors
  2 PTP600 PIDUs

  AFAIK all the mentioned gear above are floating ground

  We have this gear connected to the Netonix: Airfiber24, Epmp, PMP450

  all wireless gear is using shielded cable that is terminated in a WBMGF SS on 
the rack

  So this is the issue, we migrated everything to DC, when we connect the 
PTP600 PIDU to the rectifier, the fuse on the emerson output feeding the 
Netonix blows..not instantly.. it takes some 30-45 secs..

  im scratching my head on this one... any ideas? 