So we are moving a site form AC to DC -48

this is the setup:

Emerson Rectifier feeding:

Telco System MPLS router
Planet Fiber SW
2 Netonix DC Switches
2 SAF POE Injectors
2 PTP600 PIDUs

AFAIK all the mentioned gear above are floating ground

We have this gear connected to the Netonix: Airfiber24, Epmp, PMP450

all wireless gear is using shielded cable that is terminated in a WBMGF SS
on the rack

So this is the issue, we migrated everything to DC, when we connect the
PTP600 PIDU to the rectifier, the fuse on the emerson output feeding the
Netonix blows..not instantly.. it takes some 30-45 secs..

im scratching my head on this one... any ideas?

Reply via email to