Problem might be that you don't know for sure that the 2 120 volt lines are
actually from the two sides of the service.  There may be an easier way, but
I think you'll need an A.C. voltmeter that goes at least to 250 volts
to chec between the two hots to see that they are 
actually 240 volts apart.  They could be just 2 120s from two breakers
on the same side of the service.

Tom