Un exemple de ce que ça donne :

   
   
  NOTE:  
The power allocation for the Redundant Supervisor Engine slot is the 
greater of the Supervisor Engine power or the Line Card power in that 
slot.         
 
 
  Configuration Details
  
Slot Line Card Output Current(@42V) 
(A) Output Power 
(W) Typical Power Used 
(W) Heat Dissipation 
(BTU/Hr) 
FAN1 WS-C6509-E-FAN 5.00 210.00 168.00 843.70 
1 WS-X6748-GE-TX 7.75 325.50 260.40 1307.74 
2 WS-X6748-GE-TX 7.75 325.50 260.40 1307.74 
3 WS-X6748-GE-TX 7.75 325.50 260.40 1307.74 
4 WS-X6748-GE-TX 7.75 325.50 260.40 1307.74 
5 VS-S720-10G-3C  8.05 338.10 270.48 1358.37 
6 WS-X6748-GE-TX 8.05 338.10 270.48 1358.37 
7 WS-X6708-10G-3C 10.58 444.36 355.49 1785.28 
8 WS-X6708-10G-3C 10.58 444.36 355.49 1785.28 
9 WS-X6708-10G-3C 10.58 444.36 355.49 1785.28 
    Output Current(@42V) 
(A) Output Power 
(W) Typical Power Used 
(W) Heat Dissipation 
(BTU/Hr) 
  Total 83.84 3521.28 2817.02 14147.25  




________________________________
 De : Alexandre Legrix <a...@bragonux.net>
À : Surya ARBY <arbysu...@yahoo.fr> 
Cc : "frnog-t...@frnog.org" <frnog-t...@frnog.org> 
Envoyé le : Mercredi 18 juillet 2012 16h49
Objet : Re: [FRnOG] [TECH] Consommation électrique Cisco.
 

On Jul 18, 2012, at 4:45 PM, Surya ARBY wrote:

> Cisco Power calculator ?
> 
> http://tools.cisco.com/cpc/
> 
> Tu auras les pré requis en terme d'alim en fonction de la config du chassis.
> 
> Sinon tu as tout sur les data sheet (au moins la puissance en W des alims)
> 
> En dehors de ça le reste est confidentiel.
> 

Oh merci !

Je vais m'inscrire pour voir, si cet outil vaut réellement le coup, en espérant 
qu'on arrive à quelqu'un chose sans contrat smartnet.

Tanks Surya


---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/
---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/

Reply via email to