On 01/08/12 19:41, Home wrote:
Just checked and it is the 20amp fuse from the firewall fusebox.
As you say, it's odd that a 20amp blows before the 15amp.
Steve
Not so strange. It depends what else the 20A fuse is supplying. Assume
for argument's sake that there is another load of say 10A fed by the 20A
fuse. That would leave just 10A capacity on the 20A fuse, so in the
event of a short or overload, the 20A fuse would blow before the 15A.
If that makes any sense...
Ian
-------------------------------------------