RE: Sysdef

2000-08-28 Thread Yousif, Mohammed R
Hi All Your problem accrued because you were using different PC to configure your System. The first two filed of the IP address need to be set in the PC that runs the SysDef by using "regedit.exe" and access HKY_LOCAL_MACHINE - SYSTEM - TCP/IP ( Refer to SysDef Manual ) For your Information, on

Sysdef

2000-08-28 Thread Harshad Viradia
Hi list I have five systems with plenty of nodes. The sysdef of one of the system having 24 nodes showing incorrect IP address in hardware definition. I am using sysdef, revision 2.0. The first two filed of most of the IP address in hardware definition shows 127.000 and 158.128 instead of 151

RE: PI on AW70 v6.2 (Windows NT Work Station)

2000-08-28 Thread Balmer, Robert D. (FM)
You may want to check with Foxboro and PI regarding the version of API.. We had to get the updated API to get PI to work..Even then it took some doing Mr. Robert Balmer -Original Message- From: Eudilson Núñez Cossio [mailto:[EMAIL PROTECTED]] Sent: Monday, August 28, 2000 12:53 PM To:

PI on AW70 v6.2 (Windows NT Work Station)

2000-08-28 Thread Eudilson Núñez Cossio
Hi list, Some one have experience connecting an AW70 to PI system? We need to share the real time information of the plant with the PI server but we have problems in order to access the real time data base. We configured other DCS (under solaris) and everything works fine but with Windows NT work