Re: Integer Decimal Point Notation Question

2010-10-28 Thread John Kokidko
Dave Thanks for the reply, appreciate the quick response and insight into this issue. Looks like "DISPLAY-HINT" would be worth while place to start finding a answer. Thanks John Kokidko Dave Shield wrote: On 27 October 2010 21:39, John Kokidko wrote: Is there a method that does not

Re: Integer Decimal Point Notation Question

2010-10-28 Thread Dave Shield
On 27 October 2010 21:39, John Kokidko wrote: > Is there a method that does not involve scripting that would provide > Decimal point notations. The standard way of doing this would be to define the MIB object using a syntax that involved a suitable DISPLAY-HINT ("d-1") There's an example of this

Integer Decimal Point Notation Question

2010-10-27 Thread John Kokidko
All I have a question about output form a RFC 1628 UPS MIB. The integer output is displayed without any decimals points (See Below) Is there a method that does not involve scripting that would provide Decimal point notations. That is the output of Htz would read 60.0 instead of 600. Thanks Jo