Everything - I emphasize everything - should attach to a single point ground system. The details are contained in the EIA/TIA-607 standard, various portions of the National Electric Code, and any local codes that apply. You can see some of this at http://www.chipps.com/4/EquipmentInstallation.pptx, http://www.chipps.com/5/WirelessEquipmentInstallationOutsideTowers.pptx, and http://www.chipps.com/5/WirelessEquipmentInstallationOutsideNotTower.pptx. Each of these files is very large as they contain photographs. But you need to read the standards or have someone who has do this for you.

Ken Chipps

[EMAIL PROTECTED] wrote:
We just got some new T1's in and the phone company had us run a #6 ground
wire from our main electrical ground (not earth ground) to our server room.
 Well, I hadn't really put much though into it, but what's the best way to
incorporate that ground into our server racks?  We use raised flooring, so
should we have a ground from their block to our servers?  Should our tower
be attached to the same ground?


Thanks
Doug




--------------------------------------------------------------------------------