750 /24 = 31 amps. Sounds like it may be better to standardize on 48V. If
staying at 24V I'd recommend a 80-100A fuse in each series of batteries and
maybe a 50A or in some cases lower fuse for the site.

On Wed, Jan 5, 2022, 5:40 PM Steve Jones <thatoneguyst...@gmail.com> wrote:

> So we have some 12v 190 ah batteries and are going to be running them in
> series for 24 v and pairs in parralell if we need more capacity.
>
> Where all is fusing recomended and of what type and size?
> These will be attached to 750w 1000w or 1500w ups depending on the site.
> Most sites pull between 450 and 750 watts right now off the current
> batteries
> --
> AF mailing list
> AF@af.afmug.com