Sorry, 50A being the circuit breaker. On Wed, Jan 5, 2022, 5:51 PM Colin Stanners <cstann...@gmail.com> wrote:
> 750 /24 = 31 amps. Sounds like it may be better to standardize on 48V. If > staying at 24V I'd recommend a 80-100A fuse in each series of batteries and > maybe a 50A or in some cases lower fuse for the site. > > On Wed, Jan 5, 2022, 5:40 PM Steve Jones <thatoneguyst...@gmail.com> > wrote: > >> So we have some 12v 190 ah batteries and are going to be running them in >> series for 24 v and pairs in parralell if we need more capacity. >> >> Where all is fusing recomended and of what type and size? >> These will be attached to 750w 1000w or 1500w ups depending on the site. >> Most sites pull between 450 and 750 watts right now off the current >> batteries >> -- >> AF mailing list >> AF@af.afmug.com >> http://af.afmug.com/mailman/listinfo/af_af.afmug.com >> >
-- AF mailing list AF@af.afmug.com http://af.afmug.com/mailman/listinfo/af_af.afmug.com