It actually looks like the RSD-100C-24 should do the trick (I'm dropping to 24v, so I guess my subject line wasn't exactly correct). My normal source is out of those, according to their website they have some RSD-200C-48 units though.
On Tue, Aug 18, 2015 at 7:58 PM, George Skorup <[email protected]> wrote: > The Mean Well RSD gives 4kV i/o isolation and will work perfectly this, no > grounding issues. I think the smallest you can get in 48/48 is 200W, the > RSD-200C-48. Good luck finding some. > > > On 8/18/2015 7:20 PM, Jason McKemie wrote: > >> I'm wanting to power a mikrotik switch off of a -48v rectifier setup that >> already has some -48v equipment running on it. I'll be using a Meanwell >> DC/DC converter, which appears to not bond anything with the ground. The >> mikrotik, however, does bond the negative with ground. Do I need to keep >> the mikrotik's ground isolated from the main ground? Or is the DC/DC >> converter going to keep things from going boom? >> > >