Thanks for the great information everyone! Cheers,
Andreas Wiatowski, CEO Silo Wireless Inc. 1-866-727-4138 x-600 http://www.silowireless.com Wireless | Fibre | VoIP | PBX | IPTV On Jan 31, 2018, at 8:53 PM, Josh Baird <joshba...@gmail.com<mailto:joshba...@gmail.com>> wrote: My problem with them (SD) was that a current in-rush would trip them, and the only way to get them to work again was to power cycle them. Not fun. On Wed, Jan 31, 2018 at 8:51 PM, Mark Frost <mfr...@onq.com.au<mailto:mfr...@onq.com.au>> wrote: What dramas did you have with the SD units? Any model specifically? From: Af [mailto:af-boun...@afmug.com<mailto:af-boun...@afmug.com>] On Behalf Of Josh Baird Sent: Thursday, 1 February 2018 11:15 To: af@afmug.com<mailto:af@afmug.com> Subject: Re: [AFMUG] Dc plant conversion Good info - thanks! On Wed, Jan 31, 2018 at 7:20 PM, Seth Mattinen <se...@rollernet.us<mailto:se...@rollernet.us>> wrote: On 1/31/18 15:44, Josh Baird wrote: Do NOT use the SD series. Sager is a reputable supplier! The RSD units can be hard to find at times, but are super reliable. SD-500 and larger does do constant current limiting but with a 5 second shutoff. All of the smaller SD series do not. 5 seconds should be more than enough for startup inrush though.