Com recu chez nous à l'instant: The fire on the Clichy site is extinguished. The firemen keep it under observation. The temperature of the Florence room is 20.5 degrees. There has been no power outage in the Florence room, the impacted onduleurs are not related to the Florence room. We have just been informed that the site should be accessible during the day, this information will be confirmed in the afternoon.
On 26 Apr 2023, at 13:36, Kevin Binétruy <kevin.binet...@gmail.com> wrote: Hello, Il y a eu une com : https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share&utm_medium=member_ios Statement in Relation to Incident in our Paris Campus A fire incident has occurred in a room at one of the two data centres in our Paris campus this morning. The Fire Brigade has been in attendance and the fire is now contained. The fire response systems in the building have performed as designed and no one has been injured. A number of customers have been temporarily affected and our site team is working to restore services to those customers as soon as possible. Information Suite A L’incident Survenu sur Notre Site de Paris Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des deux centres de données de notre site parisien. Les pompiers sont intervenus rapidement et l'incendie est désormais maitrisé. Les dispositifs anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été blessé. Le service de certains de nos clients a été temporairement affecté et notre équipe sur site travaille à le rétablir le plus rapidement possible. Le mer. 26 avr. 2023 à 12:54, Fabien Ségura < fabien.seg...@widenetconsulting.fr> a écrit : Hello, qqn aurait du nouveau sur la situation à GSW ? Merci. Le 26/04/2023 11:42, « Guillaume Denoix » <frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com <mailto:guillaume.den...@gmail.com>> a écrit : Merci ! On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti <tonton...@gmail.com <mailto:tonton...@gmail.com>> wrote: La climatisation est revenue et la température dans les salle sont à nouveau OK. Le local batteries du niveau 1 au sous-sol n'est pas accessible par les pompiers. Ils refroidissent les parois pour contenir le feu mais l'incendie n'est toujours pas maîtrisé. La coupure électrique est toujours envisagée. Le mer. 26 avr. 2023 à 11:24, Rod Beck <rod.b...@unitedcablecompany.com <mailto:rod.b...@unitedcablecompany.com>> a écrit : It is probably just randomness, but France seems to have a lot of datacenter fires. -R. Roderick Beck Global Network Capacity Procurement Budapest: 36-70-605-5144 New Jersey: 908-452-8183 Email: rod.b...@unitedcablecompany.com <mailto: rod.b...@unitedcablecompany.com> www.unitedcablecompany.com <https://www.instagram.com/unitedcableco/> < https://www.instagram.com/unitedcableco/>> <https://twitter.com/unitedcableco> < https://twitter.com/unitedcableco>> <https://www.linkedin.com/company/unitedcablecompany/> < https://www.linkedin.com/company/unitedcablecompany/>> <https://unitedcablecompany.com/video> < https://unitedcablecompany.com/video>> ------------------------------ *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> < frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of Ludovic Scotti <tonton...@gmail.com <mailto:tonton...@gmail.com>> *Sent:* Wednesday, April 26, 2023 10:21 AM *To:* Arthur Mayrand <art...@mayrand.net <mailto:art...@mayrand.net>> *Cc:* Guillaume Denoix <guillaume.den...@gmail.com <mailto: guillaume.den...@gmail.com>>; frnog@frnog.org <mailto:frnog@frnog.org> < frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert < frnog-al...@frnog.org <mailto:frnog-al...@frnog.org>> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une accumulation de d'eau et qui a déclenché la fuite. L'eau de la fuite est descendue sur le local batterie et a provoqué un incendie. Le directeur du site de GS est toujours en discussion avec les pompiers pour savoir si ils coupent completement le courant du batiment concerné pour l'intervention des pompiers. Pas de fummée dans les autres salles, c'est confiné à la salle technique où se trouvent les batterie. Les pompiers sont obligés de laisser bruler les batteries avant d'intervenir. Prochain point à 11h Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand <art...@mayrand.net <mailto:art...@mayrand.net>> a écrit : Pour info, ça semble coïncider avec cet incident sur la région Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible : https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV < https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix < guillaume.den...@gmail.com <mailto:guillaume.den...@gmail.com>> a écrit : Merci pour les informations ! Heureusement qu'on a un PCIT performant :) On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti <tonton...@gmail.com <mailto:tonton...@gmail.com>> wrote: D'après les infos que j'ai, incident sur le circuit de refroidissement, une fuite qui a provoqué un début d'incendie des onduleurs du bâtiment. Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à confirmer). Ludovic Le mer. 26 avr. 2023 à 09:20, Arnaud Launay <a...@launay.org <mailto:a...@launay.org>> a écrit : Hello, Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit: Il y aurait eu un incendie sur le DC Globalswitch ce matin. Les pompiers sont sur place. Avez-vous des informations ? Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une augmentation de la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin, jusqu'à un plateau élevé à ~7h50, et une petite baisse depuis 9h. Définitivement, il s'est passé quelque chose... Arnaud. --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ <http://www.frnog.org/> -- Ludovic SCOTTI --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ <http://www.frnog.org/> --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ <http://www.frnog.org/> -- Ludovic SCOTTI --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ <http://www.frnog.org/> -- Ludovic SCOTTI --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ <http://www.frnog.org/> --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/ --------------------------- Liste de diffusion du FRnOG http://www.frnog.org/