Com recu chez nous à l'instant:

The fire on the Clichy site is extinguished. The firemen keep it under 
observation. The temperature of the Florence room is 20.5 degrees. There has 
been no power outage in the Florence room, the impacted onduleurs are not 
related to the Florence room.
We have just been informed that the site should be accessible during the day, 
this information will be confirmed in the afternoon.

On 26 Apr 2023, at 13:36, Kevin Binétruy <kevin.binet...@gmail.com> wrote:

Hello,

Il y a eu une com :

https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share&utm_medium=member_ios

Statement in Relation to Incident in our Paris Campus
A fire incident has occurred in a room at one of the two data centres in
our Paris campus this morning. The Fire Brigade has been in attendance and
the fire is now contained. The fire response systems in the building have
performed as designed and no one has been injured. A number of customers
have been temporarily affected and our site team is working to restore
services to those customers as soon as possible.

Information Suite A L’incident Survenu sur Notre Site de Paris
Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des deux
centres de données de notre site parisien. Les pompiers sont intervenus
rapidement et l'incendie est désormais maitrisé. Les dispositifs
anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été
blessé. Le service de certains de nos clients a été temporairement affecté
et notre équipe sur site travaille à le rétablir le plus rapidement
possible.

Le mer. 26 avr. 2023 à 12:54, Fabien Ségura <
fabien.seg...@widenetconsulting.fr> a écrit :

Hello, qqn aurait du nouveau sur la situation à GSW ?
Merci.


Le 26/04/2023 11:42, « Guillaume Denoix » <frnog-requ...@frnog.org
<mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com
<mailto:guillaume.den...@gmail.com>> a écrit :


Merci !


On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti <tonton...@gmail.com
<mailto:tonton...@gmail.com>> wrote:


La climatisation est revenue et la température dans les salle sont à
nouveau OK.

Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
pompiers. Ils refroidissent les parois pour contenir le feu mais
l'incendie
n'est toujours pas maîtrisé.

La coupure électrique est toujours envisagée.

Le mer. 26 avr. 2023 à 11:24, Rod Beck <rod.b...@unitedcablecompany.com
<mailto:rod.b...@unitedcablecompany.com>>
a écrit :

It is probably just randomness, but France seems to have a lot of
datacenter fires.

-R.



Roderick Beck

Global Network Capacity Procurement

Budapest: 36-70-605-5144

New Jersey: 908-452-8183

Email: rod.b...@unitedcablecompany.com <mailto:
rod.b...@unitedcablecompany.com>

www.unitedcablecompany.com

<https://www.instagram.com/unitedcableco/> <
https://www.instagram.com/unitedcableco/&gt;>
<https://twitter.com/unitedcableco> <
https://twitter.com/unitedcableco&gt;>
<https://www.linkedin.com/company/unitedcablecompany/> <
https://www.linkedin.com/company/unitedcablecompany/&gt;>
<https://unitedcablecompany.com/video> <
https://unitedcablecompany.com/video&gt;>

------------------------------
*From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
Ludovic Scotti <tonton...@gmail.com <mailto:tonton...@gmail.com>>
*Sent:* Wednesday, April 26, 2023 10:21 AM
*To:* Arthur Mayrand <art...@mayrand.net <mailto:art...@mayrand.net>>
*Cc:* Guillaume Denoix <guillaume.den...@gmail.com <mailto:
guillaume.den...@gmail.com>>; frnog@frnog.org <mailto:frnog@frnog.org> <
frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert <
frnog-al...@frnog.org <mailto:frnog-al...@frnog.org>>
*Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch

Problème de pompe d'eau du circuit de refroidissement, ce qui a généré
une
accumulation de d'eau et qui a déclenché la fuite.
L'eau de la fuite est descendue sur le local batterie et a provoqué un
incendie.
Le directeur du site de GS est toujours en discussion avec les pompiers
pour savoir si ils coupent completement le courant du batiment concerné
pour l'intervention des pompiers.
Pas de fummée dans les autres salles, c'est confiné à la salle technique
où
se trouvent les batterie.
Les pompiers sont obligés de laisser bruler les batteries avant
d'intervenir.
Prochain point à 11h

Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand <art...@mayrand.net
<mailto:art...@mayrand.net>> a
écrit :

Pour info, ça semble coïncider avec cet incident sur la région
Europe-west-9 (Paris) de Google Cloud qui est complètement
inaccessible
:



https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
<
https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV


Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
guillaume.den...@gmail.com <mailto:guillaume.den...@gmail.com>>
a écrit :

Merci pour les informations !

Heureusement qu'on a un PCIT performant :)

On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti <tonton...@gmail.com
<mailto:tonton...@gmail.com>>
wrote:

D'après les infos que j'ai, incident sur le circuit de
refroidissement,
une
fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
Ils vont arrêter le courant dans tout le bâtiment concerné sous peu
(à
confirmer).

Ludovic


Le mer. 26 avr. 2023 à 09:20, Arnaud Launay <a...@launay.org
<mailto:a...@launay.org>> a
écrit :

Hello,

Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a
écrit:
Il y aurait eu un incendie sur le DC Globalswitch ce matin.
Les pompiers sont sur place.
Avez-vous des informations ?

Sur les quelques serveurs qu'on a sur place, pas de coupure, mais
une
augmentation de
la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
jusqu'à un
plateau
élevé à ~7h50, et une petite baisse depuis 9h.

Définitivement, il s'est passé quelque chose...

Arnaud.


---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/ <http://www.frnog.org/>



--
Ludovic SCOTTI

---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/ <http://www.frnog.org/>


---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/ <http://www.frnog.org/>



--
Ludovic SCOTTI

---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/ <http://www.frnog.org/>



--
Ludovic SCOTTI



---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/ <http://www.frnog.org/>





---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/


---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/

---------------------------
Liste de diffusion du FRnOG
http://www.frnog.org/

Répondre à