Wenlei,
  The power flow routine in MATPOWER does not enforce generation limits on real 
power. Exceeding the capacity does not necessarily imply a divergence of the 
power flow.

Shri

From: <Bai>, Wenlei <wenlei_...@baylor.edu<mailto:wenlei_...@baylor.edu>>
Reply-To: MATPOWER discussion forum 
<matpowe...@list.cornell.edu<mailto:matpowe...@list.cornell.edu>>
List-Post: matpower-l@cornell.edu
Date: Wednesday, February 17, 2016 at 12:57 PM
To: "matpower-l@cornell.edu<mailto:matpower-l@cornell.edu>" 
<matpower-l@cornell.edu<mailto:matpower-l@cornell.edu>>
Subject: power flow question

Dear Ray,
I tried to modified load of ‘case9’ to exceed the total generation capacity 
purposely.
To my surprise, power flow still converges.  More specifically,  the total 
generator ‘on-line capacity’ is 820MW, while the ‘actual generation’ is 920.8MW
Why the actual generation can be larger than its capacity?

Blessings,
Wenlei