On 09/24/2014 01:51 AM, Robert Jordens wrote:
> On 09/22/2014 10:52 PM, Sébastien Bourdeauducq wrote:
>> > We cannot use the data pairs for synchronization, as the latency of the
>> > transceivers might not be the same in both directions.
> Yes we can. Just define that timing is measured wrt what actually
> happens at the (one) frontend. Such a definition is required anyway.

Yes, but then the other end will have an unknown shift wrt the
reference, e.g. you cannot pulse a RTIO channel exactly at the same time
at the core and target devices. What I mean by "synchronization" is
determining that shift and compensating for it.

Sébastien