Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Ludovic Scotti
unitedcablecompany.com>
> >>
> >> www.unitedcablecompany.com
> >>
> >> <https://www.instagram.com/unitedcableco/> <
> >> https://www.instagram.com/unitedcableco/;>
> >> <https://twitter.com/unitedcableco> <
> >> https://twitter.com/unitedcableco;>
> >> <https://www.linkedin.com/company/unitedcablecompany/> <
> >> https://www.linkedin.com/company/unitedcablecompany/;>
> >> <https://unitedcablecompany.com/video> <
> >> https://unitedcablecompany.com/video;>
> >>
> >> --
> >> *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
> >> frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
> >> Ludovic Scotti mailto:tonton...@gmail.com>>
> >> *Sent:* Wednesday, April 26, 2023 10:21 AM
> >> *To:* Arthur Mayrand mailto:art...@mayrand.net>>
> >> *Cc:* Guillaume Denoix  >> guillaume.den...@gmail.com>>; frnog@frnog.org <mailto:frnog@frnog.org>
> <
> >> frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert <
> >> frnog-al...@frnog.org <mailto:frnog-al...@frnog.org>>
> >> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch
> >>
> >> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré
> >> une
> >> accumulation de d'eau et qui a déclenché la fuite.
> >> L'eau de la fuite est descendue sur le local batterie et a provoqué un
> >> incendie.
> >> Le directeur du site de GS est toujours en discussion avec les pompiers
> >> pour savoir si ils coupent completement le courant du batiment concerné
> >> pour l'intervention des pompiers.
> >> Pas de fummée dans les autres salles, c'est confiné à la salle technique
> >> où
> >> se trouvent les batterie.
> >> Les pompiers sont obligés de laisser bruler les batteries avant
> >> d'intervenir.
> >> Prochain point à 11h
> >>
> >> Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  >> <mailto:art...@mayrand.net>> a
> >> écrit :
> >>
> >> Pour info, ça semble coïncider avec cet incident sur la région
> >> Europe-west-9 (Paris) de Google Cloud qui est complètement
> >> inaccessible
> >> :
> >>
> >>
> >>
> >>
> >>
> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
> >> <
> >>
> >>
> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
> >>
> >>
> >> Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
> >> guillaume.den...@gmail.com <mailto:guillaume.den...@gmail.com>>
> >> a écrit :
> >>
> >> Merci pour les informations !
> >>
> >> Heureusement qu'on a un PCIT performant :)
> >>
> >> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti  >> <mailto:tonton...@gmail.com>>
> >> wrote:
> >>
> >> D'après les infos que j'ai, incident sur le circuit de
> >> refroidissement,
> >> une
> >> fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
> >> Ils vont arrêter le courant dans tout le bâtiment concerné sous peu
> >> (à
> >> confirmer).
> >>
> >> Ludovic
> >>
> >>
> >> Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  >> <mailto:a...@launay.org>> a
> >> écrit :
> >>
> >> Hello,
> >>
> >> Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a
> >> écrit:
> >> Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> >> Les pompiers sont sur place.
> >> Avez-vous des informations ?
> >>
> >> Sur les quelques serveurs qu'on a sur place, pas de coupure, mais
> >> une
> >> augmentation de
> >> la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
> >> jusqu'à un
> >> plateau
> >> élevé à ~7h50, et une petite baisse depuis 9h.
> >>
> >> Définitivement, il s'est passé quelque chose...
> >>
> >> Arnaud.
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/ <http://www.frnog.org/>
> >>
> >>
> >>
> >> --
> >> Ludovic SCOTTI
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/ <http://www.frnog.org/>
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/ <http://www.frnog.org/>
> >>
> >>
> >>
> >> --
> >> Ludovic SCOTTI
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/ <http://www.frnog.org/>
> >>
> >>
> >>
> >> --
> >> Ludovic SCOTTI
> >>
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/ <http://www.frnog.org/>
> >>
> >>
> >>
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/
> >>
> >
>
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/
>


-- 
Ludovic SCOTTI

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Ludovic Scotti
L’incendie est éteint.
Les pompiers ne peuvent pas encore accéder à la salle des
onduleurs/batteries du niveau 1 car la température à l’intérieur était à
plus de 65°C (il y a 1h).
Au niveau des impacts, la MRR étant accolée à la salle qui a bien chauffé,
l'opérateur Zayo aurait été touché.
Les onduleurs/batteries qui ont brulés sont dédiés au niveau 1 donc les
autres niveaux ne sont pas concernés par d'éventuels problèmes de power.

Le mer. 26 avr. 2023 à 14:40, Alexandre der Garabedian 
a écrit :

> Merci à tous pour la visibilité que vous donnez ;-)
>
> On Wed, Apr 26, 2023 at 2:35 PM Raphaël SCHITZ  wrote:
>
> > Com recu chez nous à l'instant:
> >
> > The fire on the Clichy site is extinguished. The firemen keep it under
> > observation. The temperature of the Florence room is 20.5 degrees. There
> > has been no power outage in the Florence room, the impacted onduleurs are
> > not related to the Florence room.
> > We have just been informed that the site should be accessible during the
> > day, this information will be confirmed in the afternoon.
> >
> > On 26 Apr 2023, at 13:36, Kevin Binétruy 
> wrote:
> >
> > Hello,
> >
> > Il y a eu une com :
> >
> >
> >
> https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share_medium=member_ios
> >
> > Statement in Relation to Incident in our Paris Campus
> > A fire incident has occurred in a room at one of the two data centres in
> > our Paris campus this morning. The Fire Brigade has been in attendance
> and
> > the fire is now contained. The fire response systems in the building have
> > performed as designed and no one has been injured. A number of customers
> > have been temporarily affected and our site team is working to restore
> > services to those customers as soon as possible.
> >
> > Information Suite A L’incident Survenu sur Notre Site de Paris
> > Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des
> deux
> > centres de données de notre site parisien. Les pompiers sont intervenus
> > rapidement et l'incendie est désormais maitrisé. Les dispositifs
> > anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été
> > blessé. Le service de certains de nos clients a été temporairement
> affecté
> > et notre équipe sur site travaille à le rétablir le plus rapidement
> > possible.
> >
> > Le mer. 26 avr. 2023 à 12:54, Fabien Ségura <
> > fabien.seg...@widenetconsulting.fr> a écrit :
> >
> > Hello, qqn aurait du nouveau sur la situation à GSW ?
> > Merci.
> >
> >
> > Le 26/04/2023 11:42, « Guillaume Denoix »  > <mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com
> > <mailto:guillaume.den...@gmail.com>> a écrit :
> >
> >
> > Merci !
> >
> >
> > On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti  > <mailto:tonton...@gmail.com>> wrote:
> >
> >
> > La climatisation est revenue et la température dans les salle sont à
> > nouveau OK.
> >
> > Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
> > pompiers. Ils refroidissent les parois pour contenir le feu mais
> > l'incendie
> > n'est toujours pas maîtrisé.
> >
> > La coupure électrique est toujours envisagée.
> >
> > Le mer. 26 avr. 2023 à 11:24, Rod Beck  > <mailto:rod.b...@unitedcablecompany.com>>
> > a écrit :
> >
> > It is probably just randomness, but France seems to have a lot of
> > datacenter fires.
> >
> > -R.
> >
> >
> >
> > Roderick Beck
> >
> > Global Network Capacity Procurement
> >
> > Budapest: 36-70-605-5144
> >
> > New Jersey: 908-452-8183
> >
> > Email: rod.b...@unitedcablecompany.com  > rod.b...@unitedcablecompany.com>
> >
> > www.unitedcablecompany.com
> >
> > <https://www.instagram.com/unitedcableco/> <
> > https://www.instagram.com/unitedcableco/;>
> > <https://twitter.com/unitedcableco> <
> > https://twitter.com/unitedcableco;>
> > <https://www.linkedin.com/company/unitedcablecompany/> <
> > https://www.linkedin.com/company/unitedcablecompany/;>
> > <https://unitedcablecompany.com/video> <
> > https://unitedcablecompany.com/video;>
> >
> > --
> > *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
> > frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
> > Ludovic Scot

Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Alexandre der Garabedian
Hello,

Il semblerait que certaines équipes techniques puissent rentrer dans des
salles du L5. Je vous tiens au courant si l'accès redevient possible pour
tout le monde.

On Wed, Apr 26, 2023 at 2:40 PM Alexandre der Garabedian 
wrote:

> Merci à tous pour la visibilité que vous donnez ;-)
>
> On Wed, Apr 26, 2023 at 2:35 PM Raphaël SCHITZ  wrote:
>
>> Com recu chez nous à l'instant:
>>
>> The fire on the Clichy site is extinguished. The firemen keep it under
>> observation. The temperature of the Florence room is 20.5 degrees. There
>> has been no power outage in the Florence room, the impacted onduleurs are
>> not related to the Florence room.
>> We have just been informed that the site should be accessible during the
>> day, this information will be confirmed in the afternoon.
>>
>> On 26 Apr 2023, at 13:36, Kevin Binétruy 
>> wrote:
>>
>> Hello,
>>
>> Il y a eu une com :
>>
>>
>> https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share_medium=member_ios
>>
>> Statement in Relation to Incident in our Paris Campus
>> A fire incident has occurred in a room at one of the two data centres in
>> our Paris campus this morning. The Fire Brigade has been in attendance and
>> the fire is now contained. The fire response systems in the building have
>> performed as designed and no one has been injured. A number of customers
>> have been temporarily affected and our site team is working to restore
>> services to those customers as soon as possible.
>>
>> Information Suite A L’incident Survenu sur Notre Site de Paris
>> Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des
>> deux
>> centres de données de notre site parisien. Les pompiers sont intervenus
>> rapidement et l'incendie est désormais maitrisé. Les dispositifs
>> anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été
>> blessé. Le service de certains de nos clients a été temporairement affecté
>> et notre équipe sur site travaille à le rétablir le plus rapidement
>> possible.
>>
>> Le mer. 26 avr. 2023 à 12:54, Fabien Ségura <
>> fabien.seg...@widenetconsulting.fr> a écrit :
>>
>> Hello, qqn aurait du nouveau sur la situation à GSW ?
>> Merci.
>>
>>
>> Le 26/04/2023 11:42, « Guillaume Denoix » > <mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com
>> <mailto:guillaume.den...@gmail.com>> a écrit :
>>
>>
>> Merci !
>>
>>
>> On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti > <mailto:tonton...@gmail.com>> wrote:
>>
>>
>> La climatisation est revenue et la température dans les salle sont à
>> nouveau OK.
>>
>> Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
>> pompiers. Ils refroidissent les parois pour contenir le feu mais
>> l'incendie
>> n'est toujours pas maîtrisé.
>>
>> La coupure électrique est toujours envisagée.
>>
>> Le mer. 26 avr. 2023 à 11:24, Rod Beck > <mailto:rod.b...@unitedcablecompany.com>>
>> a écrit :
>>
>> It is probably just randomness, but France seems to have a lot of
>> datacenter fires.
>>
>> -R.
>>
>>
>>
>> Roderick Beck
>>
>> Global Network Capacity Procurement
>>
>> Budapest: 36-70-605-5144
>>
>> New Jersey: 908-452-8183
>>
>> Email: rod.b...@unitedcablecompany.com > rod.b...@unitedcablecompany.com>
>>
>> www.unitedcablecompany.com
>>
>> <https://www.instagram.com/unitedcableco/> <
>> https://www.instagram.com/unitedcableco/;>
>> <https://twitter.com/unitedcableco> <
>> https://twitter.com/unitedcableco;>
>> <https://www.linkedin.com/company/unitedcablecompany/> <
>> https://www.linkedin.com/company/unitedcablecompany/;>
>> <https://unitedcablecompany.com/video> <
>> https://unitedcablecompany.com/video;>
>>
>> --
>> *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
>> frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
>> Ludovic Scotti mailto:tonton...@gmail.com>>
>> *Sent:* Wednesday, April 26, 2023 10:21 AM
>> *To:* Arthur Mayrand mailto:art...@mayrand.net>>
>> *Cc:* Guillaume Denoix > guillaume.den...@gmail.com>>; frnog@frnog.org <mailto:frnog@frnog.org> <
>> frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert <
>&

Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Alexandre der Garabedian
Merci à tous pour la visibilité que vous donnez ;-)

On Wed, Apr 26, 2023 at 2:35 PM Raphaël SCHITZ  wrote:

> Com recu chez nous à l'instant:
>
> The fire on the Clichy site is extinguished. The firemen keep it under
> observation. The temperature of the Florence room is 20.5 degrees. There
> has been no power outage in the Florence room, the impacted onduleurs are
> not related to the Florence room.
> We have just been informed that the site should be accessible during the
> day, this information will be confirmed in the afternoon.
>
> On 26 Apr 2023, at 13:36, Kevin Binétruy  wrote:
>
> Hello,
>
> Il y a eu une com :
>
>
> https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share_medium=member_ios
>
> Statement in Relation to Incident in our Paris Campus
> A fire incident has occurred in a room at one of the two data centres in
> our Paris campus this morning. The Fire Brigade has been in attendance and
> the fire is now contained. The fire response systems in the building have
> performed as designed and no one has been injured. A number of customers
> have been temporarily affected and our site team is working to restore
> services to those customers as soon as possible.
>
> Information Suite A L’incident Survenu sur Notre Site de Paris
> Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des deux
> centres de données de notre site parisien. Les pompiers sont intervenus
> rapidement et l'incendie est désormais maitrisé. Les dispositifs
> anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été
> blessé. Le service de certains de nos clients a été temporairement affecté
> et notre équipe sur site travaille à le rétablir le plus rapidement
> possible.
>
> Le mer. 26 avr. 2023 à 12:54, Fabien Ségura <
> fabien.seg...@widenetconsulting.fr> a écrit :
>
> Hello, qqn aurait du nouveau sur la situation à GSW ?
> Merci.
>
>
> Le 26/04/2023 11:42, « Guillaume Denoix »  <mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com
> <mailto:guillaume.den...@gmail.com>> a écrit :
>
>
> Merci !
>
>
> On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti  <mailto:tonton...@gmail.com>> wrote:
>
>
> La climatisation est revenue et la température dans les salle sont à
> nouveau OK.
>
> Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
> pompiers. Ils refroidissent les parois pour contenir le feu mais
> l'incendie
> n'est toujours pas maîtrisé.
>
> La coupure électrique est toujours envisagée.
>
> Le mer. 26 avr. 2023 à 11:24, Rod Beck  <mailto:rod.b...@unitedcablecompany.com>>
> a écrit :
>
> It is probably just randomness, but France seems to have a lot of
> datacenter fires.
>
> -R.
>
>
>
> Roderick Beck
>
> Global Network Capacity Procurement
>
> Budapest: 36-70-605-5144
>
> New Jersey: 908-452-8183
>
> Email: rod.b...@unitedcablecompany.com  rod.b...@unitedcablecompany.com>
>
> www.unitedcablecompany.com
>
> <https://www.instagram.com/unitedcableco/> <
> https://www.instagram.com/unitedcableco/;>
> <https://twitter.com/unitedcableco> <
> https://twitter.com/unitedcableco;>
> <https://www.linkedin.com/company/unitedcablecompany/> <
> https://www.linkedin.com/company/unitedcablecompany/;>
> <https://unitedcablecompany.com/video> <
> https://unitedcablecompany.com/video;>
>
> --
> *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
> frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
> Ludovic Scotti mailto:tonton...@gmail.com>>
> *Sent:* Wednesday, April 26, 2023 10:21 AM
> *To:* Arthur Mayrand mailto:art...@mayrand.net>>
> *Cc:* Guillaume Denoix  guillaume.den...@gmail.com>>; frnog@frnog.org <mailto:frnog@frnog.org> <
> frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert <
> frnog-al...@frnog.org <mailto:frnog-al...@frnog.org>>
> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch
>
> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré
> une
> accumulation de d'eau et qui a déclenché la fuite.
> L'eau de la fuite est descendue sur le local batterie et a provoqué un
> incendie.
> Le directeur du site de GS est toujours en discussion avec les pompiers
> pour savoir si ils coupent completement le courant du batiment concerné
> pour l'intervention des pompiers.
> Pas de fummée dans les autres salles, c'est confiné à la salle technique
> où
> se trouvent les batterie.
> Les pompiers sont obligés de la

Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Raphaël SCHITZ
Com recu chez nous à l'instant:

The fire on the Clichy site is extinguished. The firemen keep it under 
observation. The temperature of the Florence room is 20.5 degrees. There has 
been no power outage in the Florence room, the impacted onduleurs are not 
related to the Florence room.
We have just been informed that the site should be accessible during the day, 
this information will be confirmed in the afternoon.

On 26 Apr 2023, at 13:36, Kevin Binétruy  wrote:

Hello,

Il y a eu une com :

https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share_medium=member_ios

Statement in Relation to Incident in our Paris Campus
A fire incident has occurred in a room at one of the two data centres in
our Paris campus this morning. The Fire Brigade has been in attendance and
the fire is now contained. The fire response systems in the building have
performed as designed and no one has been injured. A number of customers
have been temporarily affected and our site team is working to restore
services to those customers as soon as possible.

Information Suite A L’incident Survenu sur Notre Site de Paris
Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des deux
centres de données de notre site parisien. Les pompiers sont intervenus
rapidement et l'incendie est désormais maitrisé. Les dispositifs
anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été
blessé. Le service de certains de nos clients a été temporairement affecté
et notre équipe sur site travaille à le rétablir le plus rapidement
possible.

Le mer. 26 avr. 2023 à 12:54, Fabien Ségura <
fabien.seg...@widenetconsulting.fr> a écrit :

Hello, qqn aurait du nouveau sur la situation à GSW ?
Merci.


Le 26/04/2023 11:42, « Guillaume Denoix » mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com
<mailto:guillaume.den...@gmail.com>> a écrit :


Merci !


On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti mailto:tonton...@gmail.com>> wrote:


La climatisation est revenue et la température dans les salle sont à
nouveau OK.

Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
pompiers. Ils refroidissent les parois pour contenir le feu mais
l'incendie
n'est toujours pas maîtrisé.

La coupure électrique est toujours envisagée.

Le mer. 26 avr. 2023 à 11:24, Rod Beck mailto:rod.b...@unitedcablecompany.com>>
a écrit :

It is probably just randomness, but France seems to have a lot of
datacenter fires.

-R.



Roderick Beck

Global Network Capacity Procurement

Budapest: 36-70-605-5144

New Jersey: 908-452-8183

Email: rod.b...@unitedcablecompany.com 

www.unitedcablecompany.com

<https://www.instagram.com/unitedcableco/> <
https://www.instagram.com/unitedcableco/;>
<https://twitter.com/unitedcableco> <
https://twitter.com/unitedcableco;>
<https://www.linkedin.com/company/unitedcablecompany/> <
https://www.linkedin.com/company/unitedcablecompany/;>
<https://unitedcablecompany.com/video> <
https://unitedcablecompany.com/video;>

--
*From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
Ludovic Scotti mailto:tonton...@gmail.com>>
*Sent:* Wednesday, April 26, 2023 10:21 AM
*To:* Arthur Mayrand mailto:art...@mayrand.net>>
*Cc:* Guillaume Denoix >; frnog@frnog.org <mailto:frnog@frnog.org> <
frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert <
frnog-al...@frnog.org <mailto:frnog-al...@frnog.org>>
*Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch

Problème de pompe d'eau du circuit de refroidissement, ce qui a généré
une
accumulation de d'eau et qui a déclenché la fuite.
L'eau de la fuite est descendue sur le local batterie et a provoqué un
incendie.
Le directeur du site de GS est toujours en discussion avec les pompiers
pour savoir si ils coupent completement le courant du batiment concerné
pour l'intervention des pompiers.
Pas de fummée dans les autres salles, c'est confiné à la salle technique
où
se trouvent les batterie.
Les pompiers sont obligés de laisser bruler les batteries avant
d'intervenir.
Prochain point à 11h

Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand mailto:art...@mayrand.net>> a
écrit :

Pour info, ça semble coïncider avec cet incident sur la région
Europe-west-9 (Paris) de Google Cloud qui est complètement
inaccessible
:



https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
<
https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV


Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
guillaume.den...@gmail.com <mailto:guillaume.den...@gmail.com>>
a écrit :

Merci pour les informations !

Heureusement qu'on a un PCIT performant :)

On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti mailt

Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Kevin Binétruy
Hello,

Il y a eu une com :

https://www.linkedin.com/posts/global-switch_statement-in-relation-to-incident-in-our-activity-7056941925844541440-kzzQ?utm_source=share_medium=member_ios

Statement in Relation to Incident in our Paris Campus
A fire incident has occurred in a room at one of the two data centres in
our Paris campus this morning. The Fire Brigade has been in attendance and
the fire is now contained. The fire response systems in the building have
performed as designed and no one has been injured. A number of customers
have been temporarily affected and our site team is working to restore
services to those customers as soon as possible.

Information Suite A L’incident Survenu sur Notre Site de Paris
Un départ d’incendie s'est déclaré ce matin dans une salle de l’un des deux
centres de données de notre site parisien. Les pompiers sont intervenus
rapidement et l'incendie est désormais maitrisé. Les dispositifs
anti-incendie du bâtiment ont parfaitement fonctionné, personne n'a été
blessé. Le service de certains de nos clients a été temporairement affecté
et notre équipe sur site travaille à le rétablir le plus rapidement
possible.

Le mer. 26 avr. 2023 à 12:54, Fabien Ségura <
fabien.seg...@widenetconsulting.fr> a écrit :

> Hello, qqn aurait du nouveau sur la situation à GSW ?
> Merci.
>
>
> Le 26/04/2023 11:42, « Guillaume Denoix »  <mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com
> <mailto:guillaume.den...@gmail.com>> a écrit :
>
>
> Merci !
>
>
> On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti  <mailto:tonton...@gmail.com>> wrote:
>
>
> > La climatisation est revenue et la température dans les salle sont à
> > nouveau OK.
> >
> > Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
> > pompiers. Ils refroidissent les parois pour contenir le feu mais
> l'incendie
> > n'est toujours pas maîtrisé.
> >
> > La coupure électrique est toujours envisagée.
> >
> > Le mer. 26 avr. 2023 à 11:24, Rod Beck  <mailto:rod.b...@unitedcablecompany.com>>
> > a écrit :
> >
> >> It is probably just randomness, but France seems to have a lot of
> >> datacenter fires.
> >>
> >> -R.
> >>
> >>
> >>
> >> Roderick Beck
> >>
> >> Global Network Capacity Procurement
> >>
> >> Budapest: 36-70-605-5144
> >>
> >> New Jersey: 908-452-8183
> >>
> >> Email: rod.b...@unitedcablecompany.com  rod.b...@unitedcablecompany.com>
> >>
> >> www.unitedcablecompany.com
> >>
> >> <https://www.instagram.com/unitedcableco/> <
> https://www.instagram.com/unitedcableco/;>
> >> <https://twitter.com/unitedcableco> <
> https://twitter.com/unitedcableco;>
> >> <https://www.linkedin.com/company/unitedcablecompany/> <
> https://www.linkedin.com/company/unitedcablecompany/;>
> >> <https://unitedcablecompany.com/video> <
> https://unitedcablecompany.com/video;>
> >>
> >> --
> >> *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> <
> frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org>> on behalf of
> >> Ludovic Scotti mailto:tonton...@gmail.com>>
> >> *Sent:* Wednesday, April 26, 2023 10:21 AM
> >> *To:* Arthur Mayrand mailto:art...@mayrand.net>>
> >> *Cc:* Guillaume Denoix  guillaume.den...@gmail.com>>; frnog@frnog.org <mailto:frnog@frnog.org> <
> >> frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert <
> frnog-al...@frnog.org <mailto:frnog-al...@frnog.org>>
> >> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch
> >>
> >> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré
> une
> >> accumulation de d'eau et qui a déclenché la fuite.
> >> L'eau de la fuite est descendue sur le local batterie et a provoqué un
> >> incendie.
> >> Le directeur du site de GS est toujours en discussion avec les pompiers
> >> pour savoir si ils coupent completement le courant du batiment concerné
> >> pour l'intervention des pompiers.
> >> Pas de fummée dans les autres salles, c'est confiné à la salle technique
> >> où
> >> se trouvent les batterie.
> >> Les pompiers sont obligés de laisser bruler les batteries avant
> >> d'intervenir.
> >> Prochain point à 11h
> >>
> >> Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  <mailto:art...@mayrand.net>> a
> >> écrit :
> >>
> >> > Pour info, ça semble 

Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Fabien Ségura
Hello, qqn aurait du nouveau sur la situation à GSW ?
Merci.


Le 26/04/2023 11:42, « Guillaume Denoix » mailto:frnog-requ...@frnog.org> au nom de guillaume.den...@gmail.com 
<mailto:guillaume.den...@gmail.com>> a écrit :


Merci !


On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti mailto:tonton...@gmail.com>> wrote:


> La climatisation est revenue et la température dans les salle sont à
> nouveau OK.
>
> Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
> pompiers. Ils refroidissent les parois pour contenir le feu mais l'incendie
> n'est toujours pas maîtrisé.
>
> La coupure électrique est toujours envisagée.
>
> Le mer. 26 avr. 2023 à 11:24, Rod Beck  <mailto:rod.b...@unitedcablecompany.com>>
> a écrit :
>
>> It is probably just randomness, but France seems to have a lot of
>> datacenter fires.
>>
>> -R.
>>
>>
>>
>> Roderick Beck
>>
>> Global Network Capacity Procurement
>>
>> Budapest: 36-70-605-5144
>>
>> New Jersey: 908-452-8183
>>
>> Email: rod.b...@unitedcablecompany.com 
>> <mailto:rod.b...@unitedcablecompany.com>
>>
>> www.unitedcablecompany.com
>>
>> <https://www.instagram.com/unitedcableco/> 
>> <https://www.instagram.com/unitedcableco/;>
>> <https://twitter.com/unitedcableco> <https://twitter.com/unitedcableco;>
>> <https://www.linkedin.com/company/unitedcablecompany/> 
>> <https://www.linkedin.com/company/unitedcablecompany/;>
>> <https://unitedcablecompany.com/video> 
>> <https://unitedcablecompany.com/video;>
>>
>> --
>> *From:* frnog-requ...@frnog.org <mailto:frnog-requ...@frnog.org> 
>> mailto:frnog-requ...@frnog.org>> on behalf of
>> Ludovic Scotti mailto:tonton...@gmail.com>>
>> *Sent:* Wednesday, April 26, 2023 10:21 AM
>> *To:* Arthur Mayrand mailto:art...@mayrand.net>>
>> *Cc:* Guillaume Denoix > <mailto:guillaume.den...@gmail.com>>; frnog@frnog.org 
>> <mailto:frnog@frnog.org> <
>> frnog@frnog.org <mailto:frnog@frnog.org>>; frnog-alert 
>> mailto:frnog-al...@frnog.org>>
>> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch
>>
>> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une
>> accumulation de d'eau et qui a déclenché la fuite.
>> L'eau de la fuite est descendue sur le local batterie et a provoqué un
>> incendie.
>> Le directeur du site de GS est toujours en discussion avec les pompiers
>> pour savoir si ils coupent completement le courant du batiment concerné
>> pour l'intervention des pompiers.
>> Pas de fummée dans les autres salles, c'est confiné à la salle technique
>> où
>> se trouvent les batterie.
>> Les pompiers sont obligés de laisser bruler les batteries avant
>> d'intervenir.
>> Prochain point à 11h
>>
>> Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand > <mailto:art...@mayrand.net>> a
>> écrit :
>>
>> > Pour info, ça semble coïncider avec cet incident sur la région
>> > Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible
>> :
>> >
>> >
>> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
>>  
>> <https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV>
>> >
>> > Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
>> guillaume.den...@gmail.com <mailto:guillaume.den...@gmail.com>>
>> > a écrit :
>> >
>> >> Merci pour les informations !
>> >>
>> >> Heureusement qu'on a un PCIT performant :)
>> >>
>> >> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti > >> <mailto:tonton...@gmail.com>>
>> >> wrote:
>> >> >
>> >> > D'après les infos que j'ai, incident sur le circuit de
>> refroidissement,
>> >> une
>> >> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
>> >> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu
>> (à
>> >> > confirmer).
>> >> >
>> >> > Ludovic
>> >> >
>> >> >
>> >> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay > >> > <mailto:a...@launay.org>> a
>> écrit :
>> >> >
>> >> > > Hello,
>> >> > >
>> >> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:

Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Guillaume Denoix
Merci !

On Wed, Apr 26, 2023 at 11:39 AM Ludovic Scotti  wrote:

> La climatisation est revenue et la température dans les salle sont à
> nouveau OK.
>
> Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
> pompiers. Ils refroidissent les parois pour contenir le feu mais l'incendie
> n'est toujours pas maîtrisé.
>
> La coupure électrique est toujours envisagée.
>
> Le mer. 26 avr. 2023 à 11:24, Rod Beck 
> a écrit :
>
>> It is probably just randomness, but France seems to have a lot of
>> datacenter fires.
>>
>> -R.
>>
>>
>>
>> Roderick Beck
>>
>> Global Network Capacity Procurement
>>
>> Budapest:36-70-605-5144
>>
>> New Jersey: 908-452-8183
>>
>> Email: rod.b...@unitedcablecompany.com
>>
>> www.unitedcablecompany.com
>>
>>   <https://www.instagram.com/unitedcableco/>
>> <https://twitter.com/unitedcableco>
>> <https://www.linkedin.com/company/unitedcablecompany/>
>> <https://unitedcablecompany.com/video>
>>
>> --
>> *From:* frnog-requ...@frnog.org  on behalf of
>> Ludovic Scotti 
>> *Sent:* Wednesday, April 26, 2023 10:21 AM
>> *To:* Arthur Mayrand 
>> *Cc:* Guillaume Denoix ; frnog@frnog.org <
>> frnog@frnog.org>; frnog-alert 
>> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch
>>
>> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une
>> accumulation de d'eau et qui a déclenché la fuite.
>> L'eau de la fuite est descendue sur le local batterie et a provoqué un
>> incendie.
>> Le directeur du site de GS est toujours en discussion avec les pompiers
>> pour savoir si ils coupent completement le courant du batiment concerné
>> pour l'intervention des pompiers.
>> Pas de fummée dans les autres salles, c'est confiné à la salle technique
>> où
>> se trouvent les batterie.
>> Les pompiers sont obligés de laisser bruler les batteries avant
>> d'intervenir.
>> Prochain point à 11h
>>
>> Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  a
>> écrit :
>>
>> > Pour info, ça semble coïncider avec cet incident sur la région
>> > Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible
>> :
>> >
>> >
>> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
>> >
>> > Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
>> guillaume.den...@gmail.com>
>> > a écrit :
>> >
>> >> Merci pour les informations !
>> >>
>> >> Heureusement qu'on a un PCIT performant :)
>> >>
>> >> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti 
>> >> wrote:
>> >> >
>> >> > D'après les infos que j'ai, incident sur le circuit de
>> refroidissement,
>> >> une
>> >> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
>> >> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu
>> (à
>> >> > confirmer).
>> >> >
>> >> > Ludovic
>> >> >
>> >> >
>> >> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a
>> écrit :
>> >> >
>> >> > > Hello,
>> >> > >
>> >> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
>> >> > > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
>> >> > > > Les pompiers sont sur place.
>> >> > > > Avez-vous des informations ?
>> >> > >
>> >> > > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais
>> une
>> >> > > augmentation de
>> >> > > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
>> >> jusqu'à un
>> >> > > plateau
>> >> > > élevé à ~7h50, et une petite baisse depuis 9h.
>> >> > >
>> >> > > Définitivement, il s'est passé quelque chose...
>> >> > >
>> >> > > Arnaud.
>> >> > >
>> >> > >
>> >> > > ---
>> >> > > Liste de diffusion du FRnOG
>> >> > > http://www.frnog.org/
>> >> > >
>> >> >
>> >> >
>> >> > --
>> >> > Ludovic SCOTTI
>> >> >
>> >> > ---
>> >> > Liste de diffusion du FRnOG
>> >> > http://www.frnog.org/
>> >>
>> >>
>> >> ---
>> >> Liste de diffusion du FRnOG
>> >> http://www.frnog.org/
>> >>
>> >
>>
>> --
>> Ludovic SCOTTI
>>
>> ---
>> Liste de diffusion du FRnOG
>> http://www.frnog.org/
>>
>
>
> --
> Ludovic SCOTTI
>

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Ludovic Scotti
La climatisation est revenue et la température dans les salle sont à
nouveau OK.

Le local batteries du niveau 1 au sous-sol n'est pas accessible par les
pompiers. Ils refroidissent les parois pour contenir le feu mais l'incendie
n'est toujours pas maîtrisé.

La coupure électrique est toujours envisagée.

Le mer. 26 avr. 2023 à 11:24, Rod Beck  a
écrit :

> It is probably just randomness, but France seems to have a lot of
> datacenter fires.
>
> -R.
>
>
>
> Roderick Beck
>
> Global Network Capacity Procurement
>
> Budapest:36-70-605-5144
>
> New Jersey: 908-452-8183
>
> Email: rod.b...@unitedcablecompany.com
>
> www.unitedcablecompany.com
>
>   <https://www.instagram.com/unitedcableco/>
> <https://twitter.com/unitedcableco>
> <https://www.linkedin.com/company/unitedcablecompany/>
> <https://unitedcablecompany.com/video>
>
> --
> *From:* frnog-requ...@frnog.org  on behalf of
> Ludovic Scotti 
> *Sent:* Wednesday, April 26, 2023 10:21 AM
> *To:* Arthur Mayrand 
> *Cc:* Guillaume Denoix ; frnog@frnog.org <
> frnog@frnog.org>; frnog-alert 
> *Subject:* Re: [FRnOG] [ALERT] Incident DC Globalswitch
>
> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une
> accumulation de d'eau et qui a déclenché la fuite.
> L'eau de la fuite est descendue sur le local batterie et a provoqué un
> incendie.
> Le directeur du site de GS est toujours en discussion avec les pompiers
> pour savoir si ils coupent completement le courant du batiment concerné
> pour l'intervention des pompiers.
> Pas de fummée dans les autres salles, c'est confiné à la salle technique où
> se trouvent les batterie.
> Les pompiers sont obligés de laisser bruler les batteries avant
> d'intervenir.
> Prochain point à 11h
>
> Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  a écrit
> :
>
> > Pour info, ça semble coïncider avec cet incident sur la région
> > Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible :
> >
> >
> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
> >
> > Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
> guillaume.den...@gmail.com>
> > a écrit :
> >
> >> Merci pour les informations !
> >>
> >> Heureusement qu'on a un PCIT performant :)
> >>
> >> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti 
> >> wrote:
> >> >
> >> > D'après les infos que j'ai, incident sur le circuit de
> refroidissement,
> >> une
> >> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
> >> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
> >> > confirmer).
> >> >
> >> > Ludovic
> >> >
> >> >
> >> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit
> :
> >> >
> >> > > Hello,
> >> > >
> >> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
> >> > > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> >> > > > Les pompiers sont sur place.
> >> > > > Avez-vous des informations ?
> >> > >
> >> > > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais
> une
> >> > > augmentation de
> >> > > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
> >> jusqu'à un
> >> > > plateau
> >> > > élevé à ~7h50, et une petite baisse depuis 9h.
> >> > >
> >> > > Définitivement, il s'est passé quelque chose...
> >> > >
> >> > > Arnaud.
> >> > >
> >> > >
> >> > > ---
> >> > > Liste de diffusion du FRnOG
> >> > > http://www.frnog.org/
> >> > >
> >> >
> >> >
> >> > --
> >> > Ludovic SCOTTI
> >> >
> >> > ---
> >> > Liste de diffusion du FRnOG
> >> > http://www.frnog.org/
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/
> >>
> >
>
> --
> Ludovic SCOTTI
>
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/
>


-- 
Ludovic SCOTTI

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Rod Beck
It is probably just randomness, but France seems to have a lot of datacenter 
fires.

-R.


 
[https://lh6.googleusercontent.com/2Lt_FJczBnPSUVs0JtgFSEE6fuziTBUYnu5DNq7DbaHJYMBySeKDNp6ky9fv2ZWitaRolkQMR0HSYAjjdUM-gPjMmFr6UnBhtrqwCia4-yVzmmqhyQtc-ad4xrS_rOVnPbkMDOFfh8OhRQhNA_O0QSw]

Roderick Beck

Global Network Capacity Procurement

Budapest:36-70-605-5144

New Jersey: 908-452-8183

Email: rod.b...@unitedcablecompany.com

www.unitedcablecompany.com<http://www.unitedcablecompany.com/>

  
[https://lh6.googleusercontent.com/9R8wAqKpQlsGGeLxkitsOAGZIQucIAtkshtukANvmidSqz6q6w8bfgw1ayLaQLu77e2px7kf_Z-COzwKMwzoOaamiT8nQTWBY4SE5bJbgHvfBDpHFO2hot6tXqnoWYa3yY2p2l73e70mLuf930n9PKQ]
 <https://www.instagram.com/unitedcableco/> 
[https://lh6.googleusercontent.com/hfZwsEtrU6zRgcl2B--cHNIQoviPy66lZXM-SPu-enHxzN4PTw-dn1561xJUY_PwXLBZrbwrbT5e8un3NttT_E4IMFTa65qHiW0AufGmGjEWhkMGr-zQWJ5y20Mp7aBfGzIJtB7U8u12DWutCGFr6go]
 <https://twitter.com/unitedcableco> 
[https://lh4.googleusercontent.com/QlM9Q72tZY7lyyTh46fFRX4812LGdtEnBEFfpd4m3ybv2msBvSJCsAwwjCBCeTVniXqGwoqGsmuerW9bZZ_VYsRzJ8gVPxQEWVPa82Rs5ELajVXrNnbFlGgi6SzxOjRHT8QPmtb3UhVs_YRmxQjY3Uo]
 <https://www.linkedin.com/company/unitedcablecompany/>   
[https://lh6.googleusercontent.com/utA6pbJLZJpgC_rlNXfhviBHRjT4pyeShbRvycb8HG3_DFzbMXuo136B2hLqlphCvLhy2ZmnsrHMVAk-1hWpTRr3eDqQzfXT5VYftw_P8fzUbpgbmsVFnZf2WQVTsL97wpeVqRZbMOf7N95Eq4Up-as]
 <https://unitedcablecompany.com/video>


From: frnog-requ...@frnog.org  on behalf of Ludovic 
Scotti 
Sent: Wednesday, April 26, 2023 10:21 AM
To: Arthur Mayrand 
Cc: Guillaume Denoix ; frnog@frnog.org 
; frnog-alert 
Subject: Re: [FRnOG] [ALERT] Incident DC Globalswitch

Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une
accumulation de d'eau et qui a déclenché la fuite.
L'eau de la fuite est descendue sur le local batterie et a provoqué un
incendie.
Le directeur du site de GS est toujours en discussion avec les pompiers
pour savoir si ils coupent completement le courant du batiment concerné
pour l'intervention des pompiers.
Pas de fummée dans les autres salles, c'est confiné à la salle technique où
se trouvent les batterie.
Les pompiers sont obligés de laisser bruler les batteries avant
d'intervenir.
Prochain point à 11h

Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  a écrit :

> Pour info, ça semble coïncider avec cet incident sur la région
> Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible :
>
> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
>
> Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix 
> a écrit :
>
>> Merci pour les informations !
>>
>> Heureusement qu'on a un PCIT performant :)
>>
>> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti 
>> wrote:
>> >
>> > D'après les infos que j'ai, incident sur le circuit de refroidissement,
>> une
>> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
>> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
>> > confirmer).
>> >
>> > Ludovic
>> >
>> >
>> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit :
>> >
>> > > Hello,
>> > >
>> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
>> > > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
>> > > > Les pompiers sont sur place.
>> > > > Avez-vous des informations ?
>> > >
>> > > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une
>> > > augmentation de
>> > > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
>> jusqu'à un
>> > > plateau
>> > > élevé à ~7h50, et une petite baisse depuis 9h.
>> > >
>> > > Définitivement, il s'est passé quelque chose...
>> > >
>> > > Arnaud.
>> > >
>> > >
>> > > ---
>> > > Liste de diffusion du FRnOG
>> > > http://www.frnog.org/
>> > >
>> >
>> >
>> > --
>> > Ludovic SCOTTI
>> >
>> > ---
>> > Liste de diffusion du FRnOG
>> > http://www.frnog.org/
>>
>>
>> ---
>> Liste de diffusion du FRnOG
>> http://www.frnog.org/
>>
>

--
Ludovic SCOTTI

---
Liste de diffusion du FRnOG
http://www.frnog.org/

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Alexandre der Garabedian
Merci pour les informations !

On Wed, Apr 26, 2023 at 10:21 AM Ludovic Scotti  wrote:

> Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une
> accumulation de d'eau et qui a déclenché la fuite.
> L'eau de la fuite est descendue sur le local batterie et a provoqué un
> incendie.
> Le directeur du site de GS est toujours en discussion avec les pompiers
> pour savoir si ils coupent completement le courant du batiment concerné
> pour l'intervention des pompiers.
> Pas de fummée dans les autres salles, c'est confiné à la salle technique où
> se trouvent les batterie.
> Les pompiers sont obligés de laisser bruler les batteries avant
> d'intervenir.
> Prochain point à 11h
>
> Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  a écrit
> :
>
> > Pour info, ça semble coïncider avec cet incident sur la région
> > Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible :
> >
> >
> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
> >
> > Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix <
> guillaume.den...@gmail.com>
> > a écrit :
> >
> >> Merci pour les informations !
> >>
> >> Heureusement qu'on a un PCIT performant :)
> >>
> >> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti 
> >> wrote:
> >> >
> >> > D'après les infos que j'ai, incident sur le circuit de
> refroidissement,
> >> une
> >> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
> >> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
> >> > confirmer).
> >> >
> >> > Ludovic
> >> >
> >> >
> >> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit
> :
> >> >
> >> > > Hello,
> >> > >
> >> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
> >> > > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> >> > > > Les pompiers sont sur place.
> >> > > > Avez-vous des informations ?
> >> > >
> >> > > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais
> une
> >> > > augmentation de
> >> > > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
> >> jusqu'à un
> >> > > plateau
> >> > > élevé à ~7h50, et une petite baisse depuis 9h.
> >> > >
> >> > > Définitivement, il s'est passé quelque chose...
> >> > >
> >> > > Arnaud.
> >> > >
> >> > >
> >> > > ---
> >> > > Liste de diffusion du FRnOG
> >> > > http://www.frnog.org/
> >> > >
> >> >
> >> >
> >> > --
> >> > Ludovic SCOTTI
> >> >
> >> > ---
> >> > Liste de diffusion du FRnOG
> >> > http://www.frnog.org/
> >>
> >>
> >> ---
> >> Liste de diffusion du FRnOG
> >> http://www.frnog.org/
> >>
> >
>
> --
> Ludovic SCOTTI
>
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/
>

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Ludovic Scotti
Problème de pompe d'eau du circuit de refroidissement, ce qui a généré une
accumulation de d'eau et qui a déclenché la fuite.
L'eau de la fuite est descendue sur le local batterie et a provoqué un
incendie.
Le directeur du site de GS est toujours en discussion avec les pompiers
pour savoir si ils coupent completement le courant du batiment concerné
pour l'intervention des pompiers.
Pas de fummée dans les autres salles, c'est confiné à la salle technique où
se trouvent les batterie.
Les pompiers sont obligés de laisser bruler les batteries avant
d'intervenir.
Prochain point à 11h

Le mer. 26 avr. 2023 à 10:00, Arthur Mayrand  a écrit :

> Pour info, ça semble coïncider avec cet incident sur la région
> Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible :
>
> https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV
>
> Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix 
> a écrit :
>
>> Merci pour les informations !
>>
>> Heureusement qu'on a un PCIT performant :)
>>
>> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti 
>> wrote:
>> >
>> > D'après les infos que j'ai, incident sur le circuit de refroidissement,
>> une
>> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
>> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
>> > confirmer).
>> >
>> > Ludovic
>> >
>> >
>> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit :
>> >
>> > > Hello,
>> > >
>> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
>> > > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
>> > > > Les pompiers sont sur place.
>> > > > Avez-vous des informations ?
>> > >
>> > > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une
>> > > augmentation de
>> > > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
>> jusqu'à un
>> > > plateau
>> > > élevé à ~7h50, et une petite baisse depuis 9h.
>> > >
>> > > Définitivement, il s'est passé quelque chose...
>> > >
>> > > Arnaud.
>> > >
>> > >
>> > > ---
>> > > Liste de diffusion du FRnOG
>> > > http://www.frnog.org/
>> > >
>> >
>> >
>> > --
>> > Ludovic SCOTTI
>> >
>> > ---
>> > Liste de diffusion du FRnOG
>> > http://www.frnog.org/
>>
>>
>> ---
>> Liste de diffusion du FRnOG
>> http://www.frnog.org/
>>
>

-- 
Ludovic SCOTTI

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Arthur Mayrand
Pour info, ça semble coïncider avec cet incident sur la région
Europe-west-9 (Paris) de Google Cloud qui est complètement inaccessible :
https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY#73mBtVKKfeJGJ1yaY7hV

Le mer. 26 avr. 2023 à 09:42, Guillaume Denoix 
a écrit :

> Merci pour les informations !
>
> Heureusement qu'on a un PCIT performant :)
>
> On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti 
> wrote:
> >
> > D'après les infos que j'ai, incident sur le circuit de refroidissement,
> une
> > fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
> > Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
> > confirmer).
> >
> > Ludovic
> >
> >
> > Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit :
> >
> > > Hello,
> > >
> > > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
> > > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> > > > Les pompiers sont sur place.
> > > > Avez-vous des informations ?
> > >
> > > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une
> > > augmentation de
> > > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin,
> jusqu'à un
> > > plateau
> > > élevé à ~7h50, et une petite baisse depuis 9h.
> > >
> > > Définitivement, il s'est passé quelque chose...
> > >
> > > Arnaud.
> > >
> > >
> > > ---
> > > Liste de diffusion du FRnOG
> > > http://www.frnog.org/
> > >
> >
> >
> > --
> > Ludovic SCOTTI
> >
> > ---
> > Liste de diffusion du FRnOG
> > http://www.frnog.org/
>
>
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/
>

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Guillaume Denoix
Merci pour les informations !

Heureusement qu'on a un PCIT performant :)

On Wed, Apr 26, 2023 at 9:31 AM Ludovic Scotti  wrote:
>
> D'après les infos que j'ai, incident sur le circuit de refroidissement, une
> fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
> Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
> confirmer).
>
> Ludovic
>
>
> Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit :
>
> > Hello,
> >
> > Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
> > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> > > Les pompiers sont sur place.
> > > Avez-vous des informations ?
> >
> > Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une
> > augmentation de
> > la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin, jusqu'à un
> > plateau
> > élevé à ~7h50, et une petite baisse depuis 9h.
> >
> > Définitivement, il s'est passé quelque chose...
> >
> > Arnaud.
> >
> >
> > ---
> > Liste de diffusion du FRnOG
> > http://www.frnog.org/
> >
>
>
> --
> Ludovic SCOTTI
>
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/


---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Ludovic Scotti
D'après les infos que j'ai, incident sur le circuit de refroidissement, une
fuite qui a provoqué un début d'incendie des onduleurs du bâtiment.
Ils vont arrêter le courant dans tout le bâtiment concerné sous peu (à
confirmer).

Ludovic


Le mer. 26 avr. 2023 à 09:20, Arnaud Launay  a écrit :

> Hello,
>
> Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
> > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> > Les pompiers sont sur place.
> > Avez-vous des informations ?
>
> Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une
> augmentation de
> la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin, jusqu'à un
> plateau
> élevé à ~7h50, et une petite baisse depuis 9h.
>
> Définitivement, il s'est passé quelque chose...
>
> Arnaud.
>
>
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/
>


-- 
Ludovic SCOTTI

---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Arnaud Launay
Hello,

Le Wed, Apr 26, 2023 at 09:07:49AM +0200, Guillaume Denoix a écrit:
> Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> Les pompiers sont sur place.
> Avez-vous des informations ?

Sur les quelques serveurs qu'on a sur place, pas de coupure, mais une 
augmentation de
la température d'environ 10 à 15°C à partir de ~ 4h15 ce matin, jusqu'à un 
plateau
élevé à ~7h50, et une petite baisse depuis 9h.

Définitivement, il s'est passé quelque chose...

Arnaud.


---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Clement Cavadore
Hello,

Ouch, selon la localisation du dégat des eaux, ca pourrait faire mal.
Probablement moins qu'un incendie (et ses fumées), mais bon... bref,
bon courage à toi ainsi qu'aux autres structures impactées !

Clément

On Wed, 2023-04-26 at 09:16 +0200, Guillaume Denoix wrote:
> Bonjour Clément,
> 
> Information reçue à l'instant, ce serait plutôt un dégât des eaux.
> Nous avons une partie de nos infra KO, pas accès aux salles pour le
> moment.
> 
> A suivre
> 
> On Wed, Apr 26, 2023 at 9:11 AM Clement Cavadore <
> clem...@cavadore.net> wrote:
> > Bonjour,
> > 
> > Décidément, c'est à la mode les incendies de DC en France :-(
> > J'espère qu'il ne s'agit là que d'un départ vite maitrisé...
> > En tout cas, je n'en ai pas (encore) entendu parler de mon côté,
> > as-tu
> > plus d'informations de ton côté (notamment l'heure de départ et le
> > périmètre/ampleur éventuelle ?)
> > 
> > Merci d'avance !
> > 
> > Clément Cavadore
> > 
> > On Wed, 2023-04-26 at 09:07 +0200, Guillaume Denoix wrote:
> > > Bonjour,
> > > 
> > > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> > > 
> > > Les pompiers sont sur place.
> > > 
> > > Avez-vous des informations ?
> > > 
> > > Courage à tous !
> > > 
> > > 
> > > ---
> > > Liste de diffusion du FRnOG
> > > http://www.frnog.org/
> 
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/


---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Guillaume Denoix
Bonjour Clément,

Information reçue à l'instant, ce serait plutôt un dégât des eaux.
Nous avons une partie de nos infra KO, pas accès aux salles pour le moment.

A suivre

On Wed, Apr 26, 2023 at 9:11 AM Clement Cavadore  wrote:
>
> Bonjour,
>
> Décidément, c'est à la mode les incendies de DC en France :-(
> J'espère qu'il ne s'agit là que d'un départ vite maitrisé...
> En tout cas, je n'en ai pas (encore) entendu parler de mon côté, as-tu
> plus d'informations de ton côté (notamment l'heure de départ et le
> périmètre/ampleur éventuelle ?)
>
> Merci d'avance !
>
> Clément Cavadore
>
> On Wed, 2023-04-26 at 09:07 +0200, Guillaume Denoix wrote:
> > Bonjour,
> >
> > Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> >
> > Les pompiers sont sur place.
> >
> > Avez-vous des informations ?
> >
> > Courage à tous !
> >
> >
> > ---
> > Liste de diffusion du FRnOG
> > http://www.frnog.org/
>


---
Liste de diffusion du FRnOG
http://www.frnog.org/


Re: [FRnOG] [ALERT] Incident DC Globalswitch

2023-04-26 Par sujet Clement Cavadore
Bonjour,

Décidément, c'est à la mode les incendies de DC en France :-(
J'espère qu'il ne s'agit là que d'un départ vite maitrisé... 
En tout cas, je n'en ai pas (encore) entendu parler de mon côté, as-tu
plus d'informations de ton côté (notamment l'heure de départ et le
périmètre/ampleur éventuelle ?)

Merci d'avance !

Clément Cavadore

On Wed, 2023-04-26 at 09:07 +0200, Guillaume Denoix wrote:
> Bonjour,
> 
> Il y aurait eu un incendie sur le DC Globalswitch ce matin.
> 
> Les pompiers sont sur place.
> 
> Avez-vous des informations ?
> 
> Courage à tous !
> 
> 
> ---
> Liste de diffusion du FRnOG
> http://www.frnog.org/


---
Liste de diffusion du FRnOG
http://www.frnog.org/