RE: Letterbug Server on a Multinode System

2001-03-13 Thread Bakker, Rene
Con, In general there is some confusion in applying Micro I/A stations in a multi node environment. This is mainly due to incomplete/vague problem descriptions in CAR's about this issue. Let me try and clarify the matter: In order to be able to boot a Micro I/A (MIA in short) following needs t

Alarms when input changes.

2001-03-13 Thread Harshad Viradia
Hi list. I have more than 100 MAIN blocks configured for LIMS. CIMIO & FOXAPI is used for writing value to these MAIN blocks and displaying on graphics. The frequency of writing data is very low may be once or twice a day. I want to generate an alarms when value of any one of the MAIN block

Second Ethernet Port on the AW51D Speed setting

2001-03-13 Thread Freddy Why
List Members, I have an AW51D and have set up the second Ethernet Port. The hardware in question looks Like a FastSCSI/UTP 10/100Mbs Ethernet Interface Card and resides in PCI slot 1.( There are No Foxboro part numbers on this card

Re: 200 Series FBMs

2001-03-13 Thread Tom Lorenz
We added a new Fox I/A node to our Paper Mill in 2000 for our Mill Steam Distribution, Mill Effluent , and 300-350 KPPH Power Boiler (Coal,Sludge,Bark) processes. We replaced a Spectrum DCS. We had the node up and running in mid July, rolled 70% of the points while the process stayed in operation

RE: Second Ethernet Port on the AW51D Speed setting

2001-03-13 Thread Daryl Reynolds
Freddy Why, You did not describe the CISCO Switch. If you are connecting to the CISCO Switch you can define the individual port on the switch for 10 Mbs but the CISCO Switch should be smart enough to do this on its own. If your switch is a router (2500 Series etc.) there may be access control l

Re: 200 Series FBMs

2001-03-13 Thread alfons . vaningelgem . av
We have implemented several FBM200 (Models 241c, 204, 206, 207b and 201) in different nodes with no major problems. Issues : We are used to power our I/O modules with 24 V DC and that gives us some problems : - The input Voltage Rang of 24 V +5/-10% is a problem with battery buffered dc (up to 2

RE: Helpfile Viewer

2001-03-13 Thread Corey R Clingo
Dan- You might try something like: su - unprivileged_user_id -c netscape This is not quite as good as chroot but at least keeps them from overwriting files. Of course the real fix is for Foxboro to modify their software so it doesn't have to run as root. Corey Clingo Sr. Engineer BASF Cor

RE: Helpfile Viewer

2001-03-13 Thread Windle, John
There's a really interesting configuration file in the netscape home directory named Netscape.ad. For instance, it says that if you issue the command: netscape -remote "openURL(http://foxboro.com)" It doesn't open up a new version of Netscape, but finds an existing instance moves it to the foreg

Re: Second Ethernet Port on the AW51D Speed setting

2001-03-13 Thread Daren Bishop
Freddy, I am having the same problem. I don't have the documentation in front of me, but you have to go to the "OK" prompt and set the env (force it) for the hme? to 100, but mine still would not link up on the network at 100MBPS. It will negotiate at 100 but only

RE: Helpfile Viewer

2001-03-13 Thread Karppi, Dan
Joe, I downloaded an executable version of Htmlview.tcl and it requires a "wish interpreter" and runs using elm or pine programs which we don't have. Corey, I have started Netscape as user "browser" in group "browser" and it does obey file permissions. Unfortunately there are thousands of w

RE: Helpfile Viewer

2001-03-13 Thread Joe Sanguinetti

RE: Second Ethernet Port on the AW51D Speed setting

2001-03-13 Thread John Metsker
RE: Second Ethernet Port on the AW51D Speed setting Freddy and Daren, To have the hme 10/100 cards function properly it is necessary to install Foxboro QF 992053B.  It seems to provide most of the functionality contained in Sun patch #104212-13. Configuring a single/all hme card setti

RE: Helpfile Viewer

2001-03-13 Thread Karppi, Dan
Thank you very much Joe. Dan Dan Karppi CCST Falconbridge Limited Smelter Complex Falconbridge, Ontario Canada P0M 1S0 Phone: (705) 693-2761 ext. 3881 Fax: (705) 699-3887 mailto:[EMAIL PROTECTED] -Original Message- From: Joe Sanguinetti [ mailto:Joe

RE: Helpfile Viewer

2001-03-13 Thread Windle, John
Re: Netscape.ad file If you make the changes that you want, then copy the file to /usr/openwin/lib/app-defaults/Netscape, the changes will show up the next time you invoke Netscape. This is fine for changing text and things like that, but eliminating menubars has proven to be a little more compli