Yes.  We use one from Citel, very happy with their products.

Tushar


> On Oct 25, 2015, at 11:31 AM, Gino Villarini <ginovi...@gmail.com> wrote:
> 
> Tushar, when you say ground block you mean a surge suppressor?
> 
>> On Sunday, October 25, 2015, Tushar Patel <tpa...@ecpi.com> wrote:
>> We used to loose lot of radios too.
>> 
>> We do following now and it seems to help (loosing less).
>> 
>> At top on the tower:
>> We put all AP on stand off (MTOW-p), then we have grounding block mounted on 
>> the stand off at same level as AP, then less then 2 feet of cable going from 
>> grounding block to AP. All shielded cable and grounded to tower.
>> 
>> We have lost few ground block on tower but it seems to save radios.
>> 
>> Some ideas came from orthogone system product and their grounding guide 
>> lines.
>> 
>> At the bottom
>> 
>> Shielded cable going to grounding block and then to equipments.
>> 
>> Tushar
>> 
>> 
>> > On Oct 25, 2015, at 10:57 AM, Gino Villarini <ginovi...@gmail.com> wrote:
>> >
>> > So we are loosing radios left and right due to lightning!
>> >
>> > Typical site setup:
>> >
>> > Radios on tower grounded to tower
>> >
>> > Shielded cable
>> >
>> > Shielded patch panel - grounded
>> >
>> > Regular cat5 jumpers
>> >
>> > Wbmfg SS - grounded
>> >
>> > Regular cat5 jumpers
>> >
>> > Poe device
>> >
>> > What's wrong?
>> >
>> >

Reply via email to